Auxilliary Power While Welding

It must be noted that the above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are permitted by following Table III. The permissible currents shown assume that current is being drawn from either the 115V or 230V supply (not both at the same time). Also, the “Output Control” is set at “10” for maximum auxiliary power.

TABLE III

SIMULTANEOUS WELDING AND POWER

Output Selector

Permissible Power

Permissible Auxiliary

Setting

Watts (Unity Power

Current in Amperes

 

Factor)

@ 115V

-or- @ 230V

 

 

 

 

Max. Stick or Wire

 

 

 

Feed Setting

None

0

0

 

 

 

 

175 Stick Setting

2100

18

9

 

 

 

 

125 Stick Setting

3800

32

16

 

 

 

 

90 Stick Setting

5000

42

21

 

 

 

 

70 Stick Setting

5600

48

24

 

 

 

 

50 Stick Setting

6300

54

27

 

 

 

 

NO WELDING

8000

70

35

 

 

 

 

Standby Power Connections

The Ranger 8 is suitable for temporary, standby, or emergency power using the engine manufacturer’s recommended maintenance schedule.

The Ranger 8 can be permanently installed as a standby power unit for 230V-3 wire, single phase 35 ampere service.

(Connections must be made by a licensed electri- cian who can determine how the 115/230V power can be adapted to the particular installation and comply with all applicable electrical codes.) The

WARNING

following information can be used as a guide by the electrician for most applications (refer also to the connection diagram shown in Figure 1.)

1.Install a double pole, double throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the customer’s premises disconnect and service overcurrent protection.

2.Take necessary steps to assure load is limited to the capacity of the Ranger 8 by installing a 35 amp 230V double pole circuit breaker. Maximum rated load for the 230V auxiliary is 35 amperes. Loading above 35 amperes will reduce output voltage below the allowable -10% of rated voltage which may damage appliances or other motor-driven equipment.

3.Install a 50 amp 115/230V plug (NEMA type 14-50) to the Double Pole Circuit Breaker using No. 8,

4 conductor cable of the desired length. (The

50 amp 115/230V plug is available in the optional plug kit.)

4.Plug this cable into the 50 amp 115/230V receptacle on the Ranger 8 case front.

RANGER 8