b-6

OPERATION

b-6

 

 

 

ARC GOUGING

The RANGER® 305LPG can be used for limited arc gouging. For optimal performance, set the MODE switch to CC-STICK and the ARC CONTROL to +10.

Set the CONTROL knob to adjust output current to the desired level for the gouging electrode being used according to the ratings in the following table.

Carbon Diameter

Current Range

 

 

(DC, electrode Positive)

 

1/8"

60-90 Amps

 

5/32"

90-150 Amps

3/16"

200-250 Amps

AUXILIARY POWER:

Start the engine and set the IDLER control switch to the desired operating mode. Full power is available regardless of the welding control settings providing no welding current is being drawn.

The auxiliary power of the RANGER® 305LPG con- sists of two 20 Amp-120 VAC GFCI (5-20R) duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation. See the “MAINTE- NANCE SECTION” for detailed information on testing and resetting the GFCI receptacle.

The auxiliary power capacity is 10,000 watts Peak, 9,000 Watts continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equiva- lent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 40 Amps. The 240 VAC output can be split to provide two sepa- rate 120 VAC outputs with a max permissible current of 40 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240 V receptacle has two circuits, each of which measure 120V to neutral but are of opposite polarities and cannot be paralleled.

Simultaneous Welding and Auxiliary Power Loads The above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are specified in the following table. The permissible cur- rents shown assume that current is being drawn from either the 120 VAC or 240 VAC supply (not both at the same time).

RANGER® 305LPG Simultaneous Welding and Power Loads

 

 

Welding

Permissible Power-Watts

Permissible Auxiliary

 

 

Output-Amps

(Unity Power Factor)

Current in -Amps

 

 

 

 

 

 

 

 

 

 

@120 VAC *

@ 240 VAC

0

9000

74**

37

100

7600

70**

35

150

6500

60**

30

 

200

5300

50**

25

 

250

3800

36

18

300

1700

16

8

 

 

 

 

 

 

* Each duplex receptacle is limited to 20 amps.

**Not to exceed 40A per 120 VAC branch circuit when splitting the 240 VAC output.

RANGER® 305LPG Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

Current voltam-

Load

 

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

 

 

 

(Amps) meters

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(12)

75

(23)

125

(38)

175

(53)

300

(91)

 

20

120

2400

 

 

30

(9)

50

(15)

88

(27)

138

(42)

225

(69)

 

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

 

20

240

4800

 

 

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

 

37

240

9000

 

 

 

 

53

(16)

96

(29)

160

(49)

239

(73)

 

 

 

 

 

Conductor size is based on maximum 2.0% voltage drop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RANGER® 305LPG

Page 25
Image 25
Lincoln Electric IM10043-A manual ARC Gouging, Auxiliary Power, Ranger 305LPG Extension Cord Length Recommendations