A-6

INSTALLATION

A-6

 

 

 

REMOTE CONTROL

The VANTAGE® 575 CUMMINS is equipped with a 6- pin and a 14-pin connector. The 6-pin connector is for connecting the K857 or K857-1 Remote Control or for TIG welding, the K870 foot Amptrol or the K963-3 hand Amptrol. When in the CC-STICK or CV-WIRE modes and when a remote control is connected to the 6-pin Connector, the auto-sensing circuit automatically switches the OUTPUT control from control at the welder to remote control.

When in TOUCH START TIG mode and when a Amptrol is connected to the 6-Pin Connector, the OUTPUT dial is used to set the maximum current range of the CURRENT CONTROL of the Amptrol.

In the CV-WIRE mode, if the feeder being used has a voltage control when the wire feeder control cable is connected to the 14-Pin Connector, the auto-sensing circuit automatically makes OUTPUT CONTROL inac- tive and the wire feeder voltage control active. Otherwise, the OUTPUT CONTROL is used to preset the voltage.

The 14-pin connector is used to directly connect a wire feeder control cable. In the CV-WIRE mode, when the control cable is connected to the 14-pin con- nector, the auto-sensing circuit automatically makes the Output Control inactive and the wire feeder volt- age control active.

WARNING

NOTE: When a wire feeder with a built in welding voltage control is connected to the 14-pin connec- tor, do not connect anything to the 6-pin connec- tor.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power capacity of the VANTAGE® 575 CUMMINS is 20kVA of 50Hz three phase power pro- tected by an RCD (Residual Current Device) and a 3 phase 32 amp circuit breaker. The auxiliary power capacity in watts equivalent to volt-amperes at unity power factor.

This model has:

1 x 3 phase and neutral Residual Current Device (RCD) protection (30mA)

1 x 3 phase 32 amp Circuit Breaker

1 x 3 phase 415 volt 32 amp

2 x 1 phase 15 amp Circuit Breakers

2 x 1 phase 240 volt 15 amp per outlet

Note: The single-phase outlets are from different phases and cannot be paralleled.

The auxiliary power receptacles should only be used with three or four wire earthed type plugs or approved double insulated tools. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

STANDBY POWER CONNECTIONS

The VANTAGE® 575 CUMMINS is suitable for tempo- rary, standby or emergency power using the engine manufacturer’s recommended maintenance schedule.

The VANTAGE® 575 CUMMINS can be permanently installed as a standby power unit for 415/240 volt (50 Hz). Connections must be made by a licensed electri- cian who can determine how the 415/240 VAC power can be adapted to the particular installation and com- ply with all applicable electrical codes. The following information can be used as a guide by the electrician for most applications.

1.Install an isolation switch between the power com- pany meter and the premises disconnect.(The VANTAGE® 575 CUMMINS and the power compa- ny supplies must not be connected together).

Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

2.Take necessary steps to assure load is limited to the capacity of the VANTAGE® 575 CUMMINS by installing a 32 amp, 415 VAC three pole circuit breaker. Loading above the rated output will reduce output voltage below the allowable -10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheat- ing of the VANTAGE® 575 CUMMINS engine.

3.Install a 32 amp 3 phase plug to the triple-pole cir- cuit breaker using 6.02mm (minimum) x 4 conduc- tor cable of the desired length.(1 x 32 amp / 415 V & 2 x 15 amp / 240 V, plugs are available in the optional KA1373-2 plug kit).

4.Plug this cable into the 3 phase receptacle on the VANTAGE® 575 CUMMINS case front.

VANTAGE® 575 CUMMINS

Page 16
Image 16
Lincoln Electric IM10044 manual Remote Control, Auxiliary Power Receptacles, Standby Power Connections