Lincoln Electric IM919 manual CONNECTION OF RANGER 250 TO PREMISES, Installation

Models: IM919

1 49
Download 49 pages 39.64 Kb
Page 15
Image 15
CONNECTION OF RANGER® 250 TO PREMISES

A-7

INSTALLATION

A-7

 

 

 

CONNECTION OF RANGER® 250 TO PREMISES

240Volt

60 Hz.

3-Wire

Service

240 VOLT

POWER

120 VOLT

COMPANY

120 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

DOUBLE POLE DOUBLE THROW

SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

 

 

50AMP

 

 

240 VOLT

 

 

DOUBLE

50 AMP, 120/240

 

POLE

 

CIRCUIT

VOLT PLUG

240 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

N

LOAD

PREMISES

DISCONNECT AND

SERVICE

GROUNDOVERCURRENT PROTECTION

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

Manual backgroundWARNING

Only a licensed, certified, trained electrician should install the machine to a premises or residential electrical system. Be certain that:

•The installation complies with the National Electrical Code and all other applicable electrical codes.

•The premises is isolated and no feedback into the utility system can occur. Certain state and local laws require the premises to be isolated before the generator is linked to the premises. Check your state and local requirements.

•A double pole, double throw transfer switch in conjunction with the properly rated double throw cir cuit breaker is connected between the generator power and the utility meter.

RANGER® 250