WELDING TERMINALS

A-6

INSTALLATION

A-6

 

 

 

WELDING TERMINALS

The Ranger® 250 is equipped with a toggle switch for select- ing "hot" welding terminal when in the "WELD TERMINALS ON" position or "cold" welding terminal when in the "REMOTE- LY CONTROLLED" position.

WELDING OUTPUT CABLES

With the engine off connect the electrode and work cables to the output studs. The welding process dictates the polarity of the electrode cable. These connections should be checked periodically and tightened with a 3/4" wrench.

Table A.1 lists recommended cable sizes and lengths for rated current and duty cycle. Length refers to the distance from the welder to the work and back to the welder. Cable diameters are increased for long cable lengths to reduce voltage drops.

TABLE A-1

TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES

The auxiliary power capacity is 10,500 Watts Peak, 9500 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equivalent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 40 Amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 40 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insu- lated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.

Cable Length

0-100 Ft. (0-31 meters)

100-150 Ft. (30-46 meters)

150-200 Ft. (46-61 meters)

Cable Size for

250Amps

100% Duty Cycle

1 AWG

1AWG 1/0 AWG

STANDBY POWER CONNECTIONS

The RANGER® 250 is suitable for temporary, standby or emergency power using the engine manufacturerʼs recom- mended maintenance schedule.

The RANGER® 250 can be permanently installed as a stand- by power unit for 240 VAC, 3 wire, single phase, 40 amp ser- vice. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electri-

CABLE INSTALLATION

Install the welding cables to your RANGER® 250 as follows.

1.The engine must be OFF to install welding cables.

2.Remove the flanged nuts from the output terminals.

3.Connect the electrode holder and work cables to the weld output terminals. The terminals are identified on the case front.

4.Tighten the flanged nuts securely.

5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.

6.Check and tighten the connections periodically.

WELDING OUTPUT CABLESCAUTION

Loose connections will cause the output terminals to overheat. The terminals may eventually melt.

Do not cross the welding cables at the output terminal connection. Keep the cables isolated and separate from one another.

-----------------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power of the RANGER® 250 consists of two 20 Amp-120 VAC (5-20R) duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

cal codes.

1.Install the double-pole, double-throw switch between the power company meter and the premises disconnect. Switch rating must be the same or greater than the customerʼs premises disconnect and service over current protection.

2.Take necessary steps to assure load is limited to the capac- ity of the RANGER® 250 by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 40 amperes. Loading above the rated output will reduce output voltage below the allow- able - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in over- heating of the RANGER® 250 engine and/or alternator windings.

3.Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

4.Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER® 250 case front.