Lincoln Electric SAE-300 manual Gfci Testing and Resetting, PROCEDuRE

Models: SAE-300

1 34
Download 34 pages 61.64 Kb
Page 21
Image 21

D-4

MAINTENANCE

D-4

 

 

 

GFCI TESTING AND RESETTING

PROCEDuRE

The GFCI should be properly tested at least once every month or whenever it is tripped. To properly test and reset the GFCI :

If the GFCI has tripped, first carefully remove any load and check it for damage.

If the equipment has been shut down, it must be restarted.

The equipment needs to be operating at high idle speed and any necessary adjustments made on the control panel so that the equipment is providing at least 80 volts to the receptacle input terminals.

The circuit breaker for this receptacle must not be tripped. Reset if necessary.

Push the "Reset" button located on the GFCI. This will assure normal GFCI operation.

Plug a night-light (with an "ON/OFF" switch) or other product (such as a lamp) into the Duplex receptacle and turn the product "ON".

Push the "Test" button located on the GFCI. The night-light or other product should go "OFF".

Push the "Reset" button, again. The light or other product should go "ON" again.

If the light or other product remains "ON" when the "Test" button is pushed, the GFCI is not working prop- erly or has been incorrectly installed (miswired). If your GFCI is not working properly, contact a qualified, certified electrician who can assess the situation, rewire the GFCI if necessary or replace the device.

SAE-300®

Page 21
Image 21
Lincoln Electric SAE-300 manual Gfci Testing and Resetting, PROCEDuRE