Lochinvar 151-286 operation manual Number of Units

Models: 151-286

1 56
Download 56 pages 3.42 Kb
Page 22
Image 22

Outdoor Knight Boiler Installation & Operation Manual

3 Hydronic piping

Figure 3-9Multiple Boilers - Single Temperature Zoned with Valves

 

 

 

 

 

 

Number of Units

 

 

 

 

 

Model

2

3

4

5

6

7

8

 

 

 

 

 

 

Required Pipe Sizes

 

 

 

 

 

151

2"

2"

2-1/2" 2-1/2"

3"

3"

3-1/2"

 

 

ZONE #1

211

2"

2-1/2"

3"

3"

3-1/2"

4"

4"

 

 

286

2-1/2"

2-1/2"

3"

3-1/2"

3-1/2"

4"

5"

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

BACKFLOW REDUCING VALVE

 

ZONE #2 ZONE #3 ZONE #4

 

 

 

 

PREVENTER

PRESSURE

 

 

 

 

 

 

 

 

 

BALL VALVE

GAUGE

 

 

 

 

ZONE VALVES

 

 

 

(TYPICAL)

 

 

 

 

 

(TYPICAL)

 

 

 

MAKE UP WATER

SYSTEM SUPPLY

 

 

 

 

 

DIFFERENTIAL

 

 

 

SENSOR

 

 

 

 

 

PRESSURE BYPASS

 

 

 

(WHEN USED)

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE (IF USED)

 

 

 

 

 

 

 

 

 

 

 

AIR SEPARATOR

SYSTEM

CIRCULATOR

EXPANSION

TANK

 

MAY SUBSTITUTE LOW LOSS HEADER

 

DRAIN POINT

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

 

(TYPICAL)

 

 

 

 

 

ANTI-SCALD

HOT

 

BOILER

MIXING VALVE

WATER

 

 

OUT

 

CIRCULATOR

 

 

DOMESTIC

 

 

 

 

 

 

HOT WATER

 

 

 

CIRCULATOR

COLD

 

Y-STRAINER

 

WATER

 

(RECOMMENDED)

 

IN

 

(TYPICAL)

 

 

TEMPERATURE /

UNION

 

(TYPICAL)

 

PRESSURE

DRAIN

 

GAUGE

 

 

 

BOILER 2

BOILER 1

INDIRECT

(MEMBER 1)

(LEADER)

DHW TANK

NOTICE

IMG00375

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Indoor tank shown for illustration purposes.

22

Page 22
Image 22
Lochinvar 151-286 operation manual Number of Units