Outdoor Knight Boiler Installation & Operation Manual
4 Gas connections (continued)
WARNING
Use two wrenches when tightening gas piping at boiler (FIG.
Natural gas:
Pipe sizing for natural gas
1. Refer to Table 4A for pipe length and diameter. Based on |
rated boiler input (divide by 1,000 to obtain cubic feet per |
hour). |
a. Table 4A is only for natural gas with specific gravity |
Figure 4-2 Inlet Pipe with Backup Wrench
0.60 inches, with a pressure drop through the gas |
piping of 0.5 inches w.c. |
b. For additional gas pipe sizing information, refer to |
ANSI Z223.1 (or B149.1 for Canadian installations). |
Natural gas supply pressure requirements
1.Pressure required at the gas valve inlet pressure port:
•Maximum 14 inches w.c. with no flow (lockup) or with boiler on.
•Minimum 4 inches w.c. with gas flowing (verify during boiler startup).
2.Install 100% lockup gas pressure regulator in supply line if inlet pressure can exceed 14 inches w.c. at any time. Adjust lockup regulator for 14 inches w.c. maximum.
Propane Gas:
IMG00384
USE BACKUP WRENCH
TO PREVENT PIPE FROM
ROTATING
NOTICE | Maximum inlet gas pressure must not |
exceed the value specified. Minimum |
WARNING
Outdoor boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page 11). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe personal injury, death, or substantial property damage.
value listed is for the purposes of input |
adjustment. |
Pipe sizing for propane gas
1.Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator.
Propane Supply Pressure Requirements
1.Adjust propane supply regulator provided by the gas supplier for 14 inches w.c. maximum pressure.
2.Pressure required at gas valve inlet pressure port:
•Maximum 14 inches w.c. with no flow (lockup) or with boiler on.
•Minimum 8 inches w.c. with gas flowing (verify during boiler startup).
WARNING
Ensure that the high gas pressure regulator is at least 6 - 10 feet upstream of the appliance.