Lochinvar 2072, 402 Troubleshooting, Fault, Cause, Corrective Action, Noisy, Operation, No Pump

Models: 402 2072

1 44
Download 44 pages 17.92 Kb
Page 36
Image 36
Table 3D Troubleshooting Chart - Noisy System

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting

Table 3D Troubleshooting Chart - Noisy System

FAULT

CAUSE

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

- Gas supply problem.

• Refer

to the

Gas

Connections

Section

of the

 

 

Installation and Operation Manual for detailed

 

 

information concerning the gas supply.

 

 

 

 

 

 

- Gas/air mixture problem.

• Refer to the Checking Manifold Gas Pressure and

 

 

Combustion Analysis Procedure on pages 29 and 30 of

 

 

this

manual

for

the proper

settings.

Verify

 

 

that the vent/air intake lengths do not exceed the

 

 

maximum listed in the Venting section of the

 

 

Installation and Operation Manual.

 

 

 

 

 

 

- Dirty/damaged burner(s).

• Refer to pages 28 and 29 in this manual for the burner

Noisy

 

removal and inspection procedure. Clean or replace the

Operation

 

burner as necessary.

 

 

 

-Low water flow through the heat exchanger. • Refer to the Water Connections Section of the

Installation and Operation Manual for minimum flow rates. Verify that the appliance is piped in a primary/secondary fashion and that the appliance and system pump are running on a call for heat.

 

- Air in the piping system.

• Properly purge all air from the piping system.

 

 

 

 

- Low system water pressure.

• Verify system pressure is a minimum of 12 PSI.

 

 

 

 

 

- Faulty pump relay.

• Replace relay.

 

No Pump

 

 

 

- Faulty pump.

• Replace pump.

 

Operation -

 

Boiler Pump

 

 

 

 

 

 

System Pump

- Internal fault on control board.

• Check fuse F5.

 

or

 

• Replace main control board.

 

DHW Pump

 

 

 

 

Note: Make sure the boiler pump horse power (hp) does

 

 

not exceed 1 hp.

 

 

 

 

 

 

- System pressure exceeds relief valve

• Lower the system pressure below

the rating of

 

setting.

the supplied relief valve or replace the standard relief

 

 

valve with a higher rated valve up to the maximum

 

 

pressure of the heat exchanger.

 

Relief Valve

 

 

 

- Improperly sized expansion tank.

• Install properly sized expansion tank.

 

Opening

 

 

 

- Outlet water temperature in excess of 210°.

• Check setpoint of temperature control.

 

 

 

 

 

 

 

 

• Check temperature rise across heat exchanger. Refer to

 

 

the temperature rise chart in

the Water

 

 

Connections Section of the Installation and Operation

 

 

Manual.

 

Noisy 36 No Pump

Page 36
Image 36
Lochinvar 2072 Fault, Cause, Corrective Action, D Troubleshooting Chart - Noisy System, Operation, No Pump, DHW Pump