Lochinvar 2072 Troubleshooting, Fault, Description, Corrective Action, No Flame Ign, Flame CKT

Models: 402 2072

1 44
Download 44 pages 17.92 Kb
Page 38
Image 38
Gas Connections Section in the Installation and

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

The unit has failed to prove burner flame

• Inspect igniter and associated wiring for damage and

 

upon ignition.

connection.

Reference page 27 of this manual for

 

 

removal and cleaning procedure.

Replace

if

 

 

necessary.

 

 

 

 

 

• Check for proper electrical grounding of unit.

 

 

 

• Check incoming supply gas pressure. Refer to the

 

 

Gas Connections Section in the Installation and

 

 

Operation Manual for detailed information concerning

 

 

the gas supply.

 

 

 

 

• Verify that the tube from the gas valve to the combustion

 

 

air chamber is connected and is not damaged.

 

No Flame Ign

 

• Verify that the vent/air intake pipes are correctly

(Will require a manual

 

installed and that there are no obstructions.

 

reset. Press the RESET

 

 

 

 

 

button on the SMART

 

• Inspect the

burners. Reference pages

28 and

29

SYSTEM display to reset.)

 

of this manual for removal and cleaning procedures.

 

 

Replace if necessary.

 

 

 

 

• Refer to the Checking Manifold Gas Pressure and

 

 

Combustion Analysis Procedure on pages 29 and 30

 

 

of this manual for the proper settings.

 

 

 

 

• Check for 24 VAC to the gas valve during the ignition

 

 

attempt. If no voltage is present, check the wiring

 

 

between the gas valve and the main control board.

 

 

 

• Replace the wiring or the main control board as

 

 

necessary.

 

 

 

HSI Current Low

Amp draw of the hot surface igniter did not

• Measure the amp draw of the hot surface igniter during

(Will require a manual

meet the minimum requirement of 2.6 amps.

the trial for ignition stage. If less than 2.6 amps

reset once the condition

 

replace the hot surface igniter.

has been corrected. Press

 

• If more than 2.6 amps replace the control module.

the RESET button on the

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

Flame CKT

The main control board has detected an

• Replace the main control board.

internal fault.

 

Error

 

 

 

No Flame Ign 38 Combustion Analysis Procedure on pages 29 and 30

Page 38
Image 38
Lochinvar 2072 Troubleshooting, Fault, Description, Corrective Action, No Flame Ign, HSI Current Low, Flame CKT, Error