Lochinvar 402, 2072 Troubleshooting continued, Fault, Description, Corrective Action, Service Blk

Models: 402 2072

1 44
Download 44 pages 17.92 Kb
Page 43
Image 43
Service Blk

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

 

DESCRIPTION

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Establish a heating load to remove heat from

the

 

 

 

 

 

 

 

 

system.

 

 

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

 

 

 

 

 

 

has been properly purged from the system.

 

 

 

 

 

 

 

 

 

• Verify that the appliance is piped properly

into

the

 

 

 

 

 

 

 

 

system. Refer to the Water Connections Section of

Service Blk

While the unit is in Service Mode, the outlet

 

the Installation and Operation Manual for the proper

temperature has exceeded 185°F (85°C).

 

 

piping methods.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check 120 VAC to the pump motor on a

call

for

 

 

 

 

 

 

 

 

heat. If voltage is not present, check the wiring

 

 

 

 

 

 

 

 

leading to the main control board. Replace the main

 

 

 

 

 

 

 

 

control board if necessary.

 

 

 

 

 

 

 

 

 

• If 120 VAC is present on a call for heat

and

the

 

 

 

 

 

 

 

 

pump is not operating, replace the pump.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check 120 VAC supply to the transformer.

 

 

 

 

 

 

 

 

 

• Check wiring connections at the low voltage terminal

Low Voltage

120 VAC input to the main control board has

 

strip.

 

 

dropped below 100 VAC.

 

 

 

 

 

 

 

 

 

 

 

• Check the wire size/length to remote devices.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

Watch Dog Error

The

main control

board

has

detected

an

Cycle main power.

 

 

internal fault.

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Write EEProm

The

main control

board

has

detected

an

Cycle main power.

 

 

internal fault.

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program EEProm

The

main control

board

has

detected

an

Cycle main power.

 

 

internal fault.

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CRC Parameters

 

 

 

 

 

 

Cycle main power.

 

 

The

main control board has detected an

• Replace the main control board.

 

 

 

internal fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Restore default parameters using the PC program.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press RESET.

 

 

No Error Stored

The

main control board has detected an

Cycle main power.

 

 

 

internal fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Voltage 43 Watch Dog Error

Page 43
Image 43
Lochinvar 402 Troubleshooting continued, Fault, Description, Corrective Action, Service Blk, Low Voltage, Watch Dog Error