Lochinvar 402 Troubleshooting continued, Fault, Description, Corrective Action, Louver Proving

Models: 402 2072

1 44
Download 44 pages 17.92 Kb
Page 41
Image 41
Louver Proving

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

Louver Proving

 

 

(Lockout will reset

 

 

automatically after

 

• Check function of remote devices.

5 minutes or may be

An optional remote proving switch is not

reset immediately once

 

condition has been

making.

• Check for loose or misplaced jumper if

corrected. Press the

 

proving switch is not installed.

RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

 

Sensors equipped with an internal limit (such

• Check the tank temperature.

Tank Open

as the Lochinvar Squire® Indirect Tank), the

• Repair or replace the sensor wiring if damaged.

 

limit has opened due to temperature (195°F)

 

 

or the sensor has become disconnected.

• Replace the sensor if necessary.

 

 

 

 

 

APS Open

 

• Check air filter. Clean or replace as necessary.

(Lockout will reset

 

• Vent/air intake lengths exceed the maximum allowed

automatically after 5

 

minutes or may be

The air pressure switch did not make within

lengths.

reset immediately once

 

1 minute after the combustion air blower has

• Check for blockage or obstruction in vent/air inlet pipe

condition has been

corrected. Press the

been energized.

or at terminations.

 

RESET button on the

 

• Verify combustion air blower is operating. Replace if

SMART SYSTEM display

 

to reset.)

 

necessary.

 

 

 

APS Closed

 

 

(Lockout will reset

 

• Check for jumper on air pressure switch.

automatically after 5

 

minutes or may be

The SMART SYSTEM control sensed that

• Check for an unusually high negative draft in the vent

reset immediately once

the air pressure switch was closed before the

condition has been

combustion air blower was energized.

stack.

corrected. Press the

 

 

 

RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

 

 

• Verify that ID plug is connected properly to connector

 

 

X5 on the control module.

 

 

• Verify that the wiring in the ID plug is not cut or

 

 

damaged and that the wiring connectors are seated

 

 

properly in the plug.

Wrong ID Plug

Control module ID plug does not match the

• Verify that the number on the ID label on the control

Accept Personality Plug parameter.

panel matches the number in the Accept Personality

 

Plug parameter. If not, replace the control module.

 

 

 

 

• When replacing control modules, verify that the

 

 

number in the Accept Personality Plug parameter

 

 

matches the number on the ID label (reference page

 

 

24 of this manual). If so, press the ENTER button on

 

 

the SMART SYSTEM display. If not, replace the

 

 

control module.

Tank Open 41 APS Open

Page 41
Image 41