Lochinvar 2072 Troubleshooting, Fault, Description, Corrective Action, Manual Reset, High Limit

Models: 402 2072

1 44
Download 44 pages 17.92 Kb
Page 40
Image 40
system. Refer to the Water Connections Section of

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

 

CORRECTIVE ACTION

 

 

 

 

 

 

The outlet water temperature has exceeded

• Verify setting of adjustable high limit.

 

 

the setting of the adjustable high limit.

• Verify that the system is full of water and that all air

 

 

 

 

has been properly purged from the system.

 

 

 

• Verify that the appliance is piped properly into the

 

 

system. Refer to the Water Connections Section of

Manual Reset

 

the

Installation

and

Operation Manual

for

 

proper piping methods for the Copper-fin.

 

High Limit

 

 

 

• Check 120 VAC to the pump motor on a call for heat.

(Will require a manual

 

reset once condition has

 

If voltage is not present, check wiring leading to the

 

main control board. Replace the main control board if

been corrected. Press

 

 

necessary.

 

 

 

the RESET button on

 

 

 

 

 

 

 

 

 

 

the SMART SYSTEM

 

• If 120 VAC is present on a call for heat and the pump

display to reset.)

 

is not operating, replace the pump.

 

 

 

• If the system pump is a variable speed pump, ensure

 

 

the system flow is not less than the boiler flow.

 

 

 

• Check temperature setting of the main control board.

 

 

• Check resistance of water sensors and compare to

 

 

the tables on page 35 of this manual. Replace the

 

 

sensor if necessary.

 

 

 

 

• Replace outlet sensor or high limit.

 

 

 

 

 

 

The inlet water temperature did not exceed

• Raise temperature setpoint above 130°.

 

 

130° within 15 minutes of ignition.

• Install a 3-way valve or LTV valve per the piping

Inlet Low

 

 

diagram in the Water Connections Section of the

 

 

Installation and Operation Manual.

 

 

 

• Replace the inlet sensor.

 

 

 

 

• Replace the main control board.

 

 

 

 

 

Sensor Open

 

• Check the sensors and

their associated wiring.

 

Repair or replace the sensor or wiring if damaged.

(Will require a manual

 

Either the inlet water, outlet water, system

 

 

 

 

 

reset once the condition

• Measure the resistance of the sensors and compare

has been corrected. Press

supply, system return, or outdoor temperature

the RESET button on the

sensor has been disconnected.

the

resistance to

the tables on page 35 of

this

manual.

 

 

 

SMART SYSTEM display

 

 

 

 

 

 

 

 

 

 

to reset.)

 

• Replace the sensor if necessary.

 

 

 

 

 

 

 

Sensor Shorted

Either the inlet water, outlet water, system

• Check the sensors and their associated wiring.

(Will require a manual

supply, system return, or outdoor temperature

Repair or replace the sensor or wiring if damaged.

reset once the condition

sensor has been shorted.

• Measure the resistance of the sensors and compare

has been corrected. Press

 

the RESET button on the

 

the resistance to the tables on page 35 of this

SMART SYSTEM display

 

manual.

 

 

 

 

 

 

 

 

 

to reset.)

 

• Replace the sensor if necessary.

 

 

 

 

 

 

 

 

 

 

 

Manual Reset 40 (Will require a manual

Page 40
Image 40
Lochinvar 2072 Troubleshooting, Fault, Description, Corrective Action, Manual Reset, High Limit, Will require a manual