User’s Information Manual

4 SMART SYSTEM control module

Knight wall mount control module

Use the control panel (FIG. 4-1) to set temperatures, operating conditions, and monitor boiler operation.

Figure 4-1Control Panel

NAVIGATION DIAL

The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the NAVIGATION dial (in the center): MENU = Left SELECT Key

SETPOINTS = NAVIGATION Dial - Pressing Down SHDN = Right SELECT Key

Access modes

Adjusting parameters

NOTICE

Please note that the brackets ([]) denote

 

screen status.

User

 

The user can adjust space heating and tank target temperatures by pressing the NAVIGATION dial when “SETPOINTS” is flashing at the bottom of the display. The user can adjust the date and time, temperature units, and night setback override (if active) by pressing the LEFT SELECT [MENU] key for 5 seconds. When the user password “0000” appears, then press the RIGHT SELECT [SAVE] key (do not change the password).

Installer

Most parameters are available only to the installer, accessible only by entering the installer password, see the Knight Boiler Service Manual.

Saving parameters

Press the RIGHT SELECT [SAVE] key one time to return to the parameter listing. Press the RIGHT SELECT [HOME] key again to store the new settings and return to the Status Screen.

10

CAUTION Before changing parameters, note the settings so that the unit can be returned to

its original operating parameters.

The control uses an internal clock for the night setback feature and for logging of events. For these features to work properly, the clock must be set when the boiler is first installed or any time the boiler has been powered off for more than four (4) hours. This parameter must be accessed to set the clock.

NOTICE

The internal clock does not adjust for

Daylight Savings Time and therefore,

 

will require a manual adjustment.

To set the clock, access the clock menu as described in the User section. Rotate the NAVIGATION dial (if needed) until the arrow (>) is pointing to “TIME & DATE”. Press the NAVIGATION dial once. If the date and time are incorrect, press the NAVIGATION dial again. The hours value will begin flashing. Rotate the NAVIGATION dial until the hour and AM/PM values are correct. Press the NAVIGATION dial again. The minutes value will begin flashing. Rotate the NAVIGATION dial to adjust the minutes. Repeat this procedure to adjust the month, date and year. Save the new settings as described in the Saving Parameters section (this page).

Page 10
Image 10
Lochinvar 51 - 211 manual Smart System control module, User, Installer

51 - 211 specifications

Lochinvar 51-211 is a notable model in the realm of high-performance heating solutions, designed to efficiently meet commercial and residential hot water demands. This innovative water heater stands out due to its capacity, advanced technologies, and energy efficiency, making it a preferred choice for many.

One of the primary features of the Lochinvar 51-211 is its impressive output. With a 211,000 BTU input and a robust design, it is capable of delivering a substantial amount of hot water quickly, which is essential in applications where hot water demand fluctuates significantly. This unit is particularly suitable for large residential homes, restaurants, and other commercial settings where high-volume hot water is critical.

The Lochinvar 51-211 incorporates cutting-edge technology to optimize its performance. It features a stainless steel heat exchanger that not only enhances durability but also improves heat transfer efficiency. This construction provides not only longevity but also minimizes maintenance needs over the lifespan of the unit. Additionally, its smart control system allows for precise temperature control and monitoring, ensuring that users can easily customize settings according to their needs.

Energy efficiency is a cornerstone of the Lochinvar brand, and the 51-211 model is no exception. It achieves a high Energy Factor (EF), which translates to lower energy costs and reduced environmental impact. This unit is also designed to meet stringent efficiency standards, making it an ideal option for environmentally conscious consumers.

Another characteristic of the Lochinvar 51-211 is its versatility in installation. It can be installed in various configurations, allowing for flexible integration into existing systems. Furthermore, its compact design means it can fit into tight spaces without compromising functionality, making it perfect for urban settings where space is often a premium.

Safety features are also a priority in the design of the Lochinvar 51-211. The unit incorporates built-in safeguards, including flue gas monitoring and a vent system designed to prevent backdrafts, ensuring reliable and safe operation for users.

In summary, the Lochinvar 51-211 water heater combines high BTU output, advanced stainless steel technology, excellent energy efficiency, versatile installation options, and safety features. These attributes make it a top choice for anyone in need of a dependable and efficient hot water solution. With Lochinvar’s commitment to quality, users can feel confident that this unit will provide consistent performance for years to come.