All installations and services must be performed by qualified service personnel.
MAIN
BURNER
OPERATION
CALL
FOR HEAT
SATISFIED
END OF CYCLE
AFTER
WHEN THERMOSTAT IS SATISFIED, CONTACTS OPEN AND THE GAS VALVE IS
AFTER THE
THE RETRY SEQUENCE PROVIDES A 60 SECOND WAIT BEFORE IGNITION RETRY. RETRY IS ATTEMPTED WITH AN ADDITIONAL 10 SECONDS OF IGNITOR
IF IGNITION ATTEMPT IS
UNSUCCESSFUL, ONE
MORE RETRY WILL BE
MADE BEFORE THE
CONTROL BOARD GOES
INTO SYSTEM LOCKOUT.
IF FLAME IS DETECTED,
THEN LOST, THE CONTROL BOARD WILL REPEAT THE INITIAL IGNITION SEQUENCE FOR A TOTAL OF SIX RECYCLES. AFTER SIX UNSUCCESSFUL RECYCLE ATTEMPTS, THE CONTROL WILL GO INTO SYSTEM LOCKOUT.
IF SYSTEM IS IN LOCKOUT, THE MODULE WILL RESET ITSELF AFTER 60 MINUTES OR MAY BE MANUALLY RESET BY INTERRUPTING THE POWER TO THE FURNACE AT THE DISCONNECT OR INTERRUPTING THE CALL FOR HEAT AT THE THERMOSTAT. IF THIS DOES NOT RESTART THE SYSTEM,
REFER TO THE TROUBLESHOOTING
SECTION OF THIS MANUAL.