Lopi 1750 owner manual Mobile Home Requirements, Stove Installation for qualified installers only

Models: 1750

1 36
Download 36 pages 11.09 Kb
Page 14
Image 14
Mobile Home Requirements

14

Stove Installation (for qualified installers only)

Mobile Home Requirements

Outside air must be installed - see "Outside Air Requirements" on page 12

Chimney connector and chimney must be one of the following types:

AMERI-TEC model DCC with model HS chimney

DURAVENT model DVL with DURATEC or DURA-PLUS chimney

GSW Super Chimney Twenty-One connected directly to appliance

I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector

METALFAB model DW connector with TG chimney

OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney

SECURITY model DP connector with SECURITY model ASHT or S2100 chimney

SELKIRK METALBESTOS model DS connector with model SSII chimney

Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

Stove placement must maintain the following clearances to combustibles (drywall, furniture, etc.)

B

E

C

A

 

 

D

 

 

 

 

F

 

 

C

Measure all clearances from the

nearest edge of the stove top.

Figure 9

Minimum Clearance

Reduced Clearance

(See the illustration above)

Connector

 

 

 

A

Sidewall to stove

15"

B

Backwall to stove

6"

C

Cornerwall to stove

6-1/2"

D

Connector to sidewall

23-1/2"

E

Connector to backwall

8-1/4"

F

Connector to cornerwall

15"

If using offsets, use the connector clearance listed in Figure 10, not the connector manufacturer's clearance.

The appliance must be secured to the floor (consult your building official). Secure the outside air boot to the floor and stove to insure the stove does not dislocate.

Mobile home installations require a spark arrester at the

chimney termination.

The appliance must be grounded to the chassis of the mobile home (consult your building official).

WARNING:DO NOT INSTALL IN SLEEPING ROOM.

CAUTION:THE STRUCTURAL INTEGRITY OF THE MOBILE

HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.

12” Min.

Connector Clearance (as outlined above)

Stove Clearance (as outlined above)

Figure 10

© Travis Industries

100-01179

4060926

Page 14
Image 14
Lopi 1750 owner manual Mobile Home Requirements, Stove Installation for qualified installers only