Lopi 1750 Floor Protection Requirements, Stove Placement Requirements, Clearances, Singlewall

Models: 1750

1 36
Download 36 pages 11.09 Kb
Page 8
Image 8
Floor Protection Requirements

8

Stove Installation (for qualified installers only)

Floor Protection Requirements

Stove must be placed on the Travis Industries legs or Pedestal.

Floor protection must extend 6" to the sides and rear of the stove and 16" to the front of the stove (36" wide by 45-1/2" deep - see Figure 2 and Figure 3). NOTE: when installed with reduced- clearance connector, the clearance to the backwall is less than 6". In this case the floor protection must extend to the wall.

Floor protection must be non-combustible and at least .018" thick (26 guage).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.

Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove

If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"

Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

The following clearances must be met (see Figure 2 and Figure 3)

 

 

 

 

 

 

Minimum Clearance

Singlewall

Reduced

 

 

 

Connector

Clearance*

 

 

 

 

 

 

A

Sidewall to stove

15"

13"

 

B

Backwall to stove

15”

4-1/4"

 

C

Cornerwall to stove

15"

6-1/2"

 

D

Connector to sidewall

24"

21-1/2"

 

E

Connector to backwall

17-3/4"

6-1/2"

 

F

Connector to cornerwall

24"

15"

 

 

 

 

 

*Reduced clearance installations require one of the chimneys and connectors listed below:

AMERI-TEC model DCC with model HS chimney

DURAVENT model DVL with DURATEC or DURA-PLUS chimney

GSW Super Chimney Twenty-One connected directly to appliance

I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector

METALFAB model DW connector with TG chimney

OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney

SECURITY model DP connector with SECURITY model ASHT or S2100 chimney

SELKIRK METALBESTOS model DS connector with model SSII chimney

Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

NOTE: Mobile Home installations must use the reduced clearance connector and clearances listed above.

NOTE: Standard residential installations with reduced clearance connector may use the “Connector to Wall” clearance determined by the connector manufacturer if approved by local code. This clearance is established by the connector manufacturer and falls under the connector manufacturer’s listing. “Stove to Wall” clearances must always be met.