12 | Stove Installation (for qualified installers only) |
Chimney Termination Requirements
•Must have an approved cap (to prevent water from entering)
•Must not be located where it will become plugged by snow or other material
•Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see Figure 6)
Slanted Roofs
Chimney must extend 3' above the roof
Flat
Chimney must extend 3' above the roof
Chimney must extend 2' above any portion of the roof within 10' of the chimney
Chimney must extend 2' above any portion of the roof within 10' of the chimney
Figure 6
Outside Air Requirements
•Required for mobile homes & in certain localities (check with building officials)
•Must not be drawn from an enclosed space (garage, unventilated crawl space)
•Requires the optional outside air connector or pedestal.
Pedestal may be used to direct air from below the stove. See the pedestal instructions for complete details
When using outside air, find a location where the chimney and outside air hole do not interfere with structural members of the home.
The pedestal has an air opening for use with the outside air connections. This allows air to be drawn from behind the pedestal
Air may be drawn from a ventilated crawl space or use an air duct.
Outside Air
Connector
Outside air entrance must be placed so it does not become blocked by snow.
Figure 7