Marathon F200060 manual Transmit from Host or Master

Models: F200060

1 23
Download 23 pages 21.69 Kb
Page 14
Image 14

The following is an example of a function 03 call for data at memory location 03. The value returned by the instrument is the hex value 1E.

Transmit from Host or Master

 

Address

Cmd

Reg

Reg

Count

Count

CRC

CRC

 

 

 

HI

LO

HI

LO

HI

LO

01

03

00

03

00

01

74

0A

 

 

 

Response from Transmitter

 

 

 

 

Address

Cmd

Byte

Byte

 

Data

Data

CRC

CRC

 

 

 

 

Count

Count

 

HI

LO

HI

Lo

 

 

 

 

HI

LO

 

 

 

 

 

 

 

01

03

00

02

 

00

1E

38

4C

 

Note that all the values are interpreted as hexadecimal values. The CRC calculation is based on the A001 polynomial for RTU Modbus. The function 04 command structure is similar to the 03 structure.

The following is an example of a function 06 call to change data in register 01 to 200. The response from the instrument confirms the new value as being set.

Transmit from Host or Master

 

Address

Cmd

Reg

Reg

Data

Data

CRC

 

CRC

 

 

 

 

HI

LO

HI

LO

HI

 

LO

 

 

01

06

00

01

00

C8

D9

 

9C

 

 

 

Response from Transmitter

 

 

 

 

 

Address

Cmd

Reg

Reg

Data

Data

 

CRC

CRC

 

 

 

 

HI

LO

HI

LO

 

HI

LO

 

 

01

06

00

01

00

C8

 

D9

 

9C

 

The Transmitter will respond to several error conditions. The three exception codes that will generate a response from the instrument are:

01 – Illegal Function

02 - Illegal Data Address

03 – Illegal Data Value

04 – Slave Device Failure

The response from the Transmitter with an exception code will have the most significant bit of the requested function set followed by the exception code and the high and low CRC bytes.

Page 11 of 23

11/14/2006

Rev. 14

Page 14