Marathon F200060 manual Page 15 of, High Byte, Analog Output

Models: F200060

1 23
Download 23 pages 21.69 Kb
Page 18
Image 18
HIGH BYTE, ANALOG OUTPUT 2

HEX

DEC

BLOCK 0

PARAMETER DESCRIPTION

READ/WRITE

 

 

 

 

HIGH BYTE, ANALOG OUTPUT 2

 

 

 

 

 

 

BITS 8 – 12

 

 

 

 

 

 

0000

= N/A

 

 

 

 

 

 

0001

= Temperature

 

 

 

 

 

 

0010

= Linear Input A

 

 

 

 

 

 

0011

= Carbon value

 

 

 

 

 

 

0100

= Dewpoint value

 

 

 

 

 

 

0101

= Oxygen value

 

 

 

 

 

 

0110

= Redox value

 

 

 

 

 

 

0111

= Output Power

 

 

 

 

 

 

1000

= Control Output 1

 

 

 

 

 

 

1001

= Control Output 2

 

 

 

 

 

 

1010

= Linear Input B

 

 

 

 

 

 

1011

= Programmable*

 

 

 

 

 

 

*For Reference Number and Programmable ,

 

 

 

 

 

 

write required output value into DACV2, where

 

 

 

 

 

 

DACV2 = 0 is minimum output and

 

 

 

 

 

 

DACV2 = 4096 is maximum output.

 

 

 

 

 

 

BITS 13 – 15 SPARE

 

 

 

 

 

 

Special case: If Analog Output 1 = CONTROL

 

 

 

 

 

 

OUTPUT 1 and Analog Output 2 = CONTROL

 

 

 

 

 

 

OUTPUT 2 and the Control Mode is dual, then

 

 

 

 

 

 

Analog Output 1 is 4-20ma for 0 to +100% PO

 

 

 

 

 

 

and Analog Output 2 is 4-20ma for 0 to -100%

 

 

 

 

 

 

PO.

 

 

 

0C

12

 

DAC_OFFSET_1

DAC 1 OFFSET CALIBRATION

READ/WRITE

 

 

 

 

 

 

 

 

 

0D

13

 

DAC_SPAN_1

DAC 1 SPAN CALIBRATION

READ/WRITE

 

0E

14

 

DAC_OFFSET_2

DAC2 OFFSET CALIBRATION

READ/WRITE

 

 

 

 

 

 

 

 

 

 

 

0F

15

 

DAC_SPAN_2

DAC2 SPAN CALIBRATION

READ/WRITE

 

10

16

 

AOUTOF1

ANALOG OUTPUT 1 OFFSET

READ/WRITE

 

 

 

 

 

Minimum source value that correlates to

 

 

 

 

 

 

minimum Analog Output of 4 mA. The source

 

 

 

 

 

 

value is based on the selection in ASRC lower

 

 

 

 

 

 

byte

 

 

 

11

17

 

AOUTRN1

ANALOG OUTPUT 1 RANGE

READ/WRITE

 

 

 

 

 

Maximum source value that correlates to

 

 

 

 

 

 

maximum Analog Output of 20 mA. The

 

 

 

 

 

 

source value is based on the selection in

 

 

 

 

 

 

ASRC lower byte where

 

 

 

 

 

 

 

 

 

 

12

18

 

AOUTOF2

ANALOG OUTPUT 2 OFFSET

READ/WRITE

 

 

 

 

 

Minimum source value that correlates to

 

 

 

 

 

 

minimum Analog Output of 4 mA. The source

 

 

 

 

 

 

value is based on the selection in ASRC upper

 

 

 

 

 

 

byte

 

 

 

13

19

 

AOUTRN2

ANALOG OUTPUT 2 RANGE

READ/WRITE

 

 

 

 

 

Maximum source value that correlates to

 

 

 

 

 

 

maximum Analog Output of 20 mA. The

 

 

Page 15 of 23

11/14/2006

Rev. 14

Page 18
Image 18
Marathon F200060 manual Page 15 of, High Byte, Analog Output