Marathon F200060 manual Page 16 of

Models: F200060

1 23
Download 23 pages 21.69 Kb
Page 19
Image 19
Page 16 of 23

HEX

DEC

BLOCK 0

PARAMETER DESCRIPTION

READ/WRITE

 

 

 

 

source value is based on the selection in

 

 

 

 

 

 

ASRC upper byte where

 

 

 

 

 

 

 

 

 

14

20

 

SPARE

SPARE

READ/WRITE

 

15

21

 

SPARE

SPARE

READ/WRITE

 

 

 

16

22

 

SPARE

SPARE

READ/WRITE

 

 

 

 

 

 

 

 

17

23

 

TEMPFIL

Temperature Input Filter in seconds

READ/WRITE

 

 

 

 

 

Range = 0 to 3276. The higher the number

 

 

 

 

 

 

the faster the reading update.

 

 

 

 

 

 

DEFAULT = 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOCK 1

 

 

HEX

DEC

 

PARAMETER

DESCRIPTION

READ/WRITE

 

18

24

 

MVFIL

Millivolt Input Filter in seconds

READ/WRITE

 

 

 

 

 

Range = 0 to 3276. The higher the number

 

 

 

 

 

 

the faster the reading update.

 

 

 

 

 

 

DEFAULT = 1000

 

 

19

25

 

AZERO

LINEAR OFFSET, Y INTERCEPT LINEAR

READ/WRITE

 

 

 

 

 

SCALING FOR INPUT A

 

 

1A

26

 

ANUM

LINEAR SPAN VALUE FOR INPUT A

READ/WRITE

 

 

 

 

 

 

 

 

1B

27

 

BZERO

LINEAR OFFSET, Y INTERCEPT LINEAR

READ/WRITE

 

 

 

 

 

SCALING FOR INPUT B

 

 

1C

14

 

BNUM

LINEAR SPAN VALUE FOR INPUT B

READ/WRITE

 

1D

15

 

PROC

This value is the calculated process value

READ ONLY

 

 

 

 

 

shown as an integer. The decimal point and

 

 

 

 

 

 

exponent values are required to determine the

 

 

 

 

 

 

actual scaled value.

 

 

 

 

 

 

Range = -999 to 9999.

 

 

 

 

 

 

For example: If the process = oxygen, display

 

 

 

 

 

 

decimal point = 2, and exponent = 6, and

 

 

 

 

 

 

PROC = 1234, then the actual value and

 

 

 

 

 

 

displayed as 12.34 ppm.

 

 

1E

16

 

COLDJCT

COLD JUNCTION

READ ONLY

 

 

 

 

 

Where 1 COUNT = 1°F (°C), RANGE = -99 TO

 

 

 

 

 

 

255°F (°C). Note this parameter is an

 

 

 

 

 

 

unsigned integer.

 

 

1F

17

 

TEMP

MEASURED TEMPERATURE

READ ONLY

 

 

 

 

 

Where temperature is presented in degrees C

 

 

 

 

 

 

or F, based on the C/F setting. Note this

 

 

 

 

 

 

parameter is an unsigned integer of

 

 

 

 

 

 

temperature -2721 = 62815

 

 

 

 

 

 

Range = max / min range of selected

 

 

 

 

 

 

thermocouple.

 

 

20

18

 

MV

MEASURED MILLIVOLT

READ ONLY

 

 

 

 

 

Where this value is scaled in 0.1 mV

 

 

 

 

 

 

increments, i.e. 10001 = 1000.1.

 

 

 

 

 

 

Range = 0 to 2000 mV.

 

 

21

19

 

DACV1

ANALOG OUTPUT 1

READ/WRITE

 

 

 

 

 

0 to 4095 is 4 to 20 mA In dual mode 4mA = -

 

 

 

 

 

 

100, 12mA = 0, 20mA = +100

 

 

Page 16 of 23

11/14/2006

Rev. 14

Page 19
Image 19
Marathon F200060 manual Page 16 of