CHAPTER 5 M400R Main Cabinet

Installation specifications

Table 5.5 Installation Specifications of M400R

Item

 

Specification

 

 

 

 

 

Mass

 

Up to 65kg (approx.143 lb)

 

 

 

 

Power condition

Input voltage

Single phase

Single phase

 

 

100 to 120 VAC

200 to 240 VAC

 

 

(+-10%)

(+-10%)

 

Input frequency

50/60 Hz (+2 to -4%)

 

 

 

 

 

Maximum consumption current

7.5 A

3.75 A

 

 

 

Leakage current (1 for each cable)

3.5 mA or less

3.5 mA or less

 

 

 

 

Ground resistance

 

100ohm or less ( class C installation standard)

 

 

 

 

Temperature condition

Operating

5 to 35 degrees Celsius (+41 to +95 F) (*1)

 

 

 

 

 

Not operating

0 to 50 degrees Celsius (+32 to +122F)

 

 

 

 

Humidity condition

Operating

20 to 80%RH (no condensation)

 

 

 

 

 

Not operating

8 to 80% RH (no condensation)

 

 

 

 

Vibrations condition

Operating

0.2 G

 

 

 

 

 

 

Idle

0.4 G

 

 

 

 

 

Noise

 

47 db (A) (*2)

 

 

 

 

 

Installation

 

Rack mount type (7pitches)

 

 

 

 

*1: If the ambient temperature exceeds 35 degrees Celsius (+95F) during operation, a warning message is displayed. Take steps to rectify the problem immediately.

*2: The indicated noise is the mean value of the measurements obtained in an anechoic chamber with less echoic influence. The actual noise measured at the installation site may be greater than the indication noise due to surrounding noise and echoes.