Temporary Manual Hose Temperature Control

Temporary Manual Hose Temperature Control

If T6DH error code appears from a break in the hose RTD cable or FTS sensor, follow the steps for temporary manual hose temperature control. Repair or replace the hose RTD cable or FTS as soon as job is finished.

1.Connect the spare RTD (15V837), shipped with the system, to the Fluid Temperature Sensor (FTS) cables (SC) at the Reactor Fluid Manifold (FM).

A

SC

B

15V837

2.Insert the RTD sensor probe between the two hoses where the scuff guard ends.

3.Lower the hose temperature setpoint on the system ADM screen by (20°F (-6°C). Push probe into the hose bundle at least 3 in. (76 mm).

4.Do not leave the RTD tip probe exposed to air or a hose overtemperature condition may occur.

NOTICE

To prevent overheating material and damaging the hoses, do not leave the spare RTD between the two hoses after the job is complete.

5.Repair or replace the hose RTD cable or FTS as soon as the job is finished.