2.4.2.2 Single-Phase (Phase A, B) Connection

ACM100 User’s Manual

a.Connect the black wire to pin 7 (IA+) on the ACM100

b.Connect the white wire to pin 8 (IA-) on the ACM100

c.Disconnect the hot wire from the AC power source and place it through the hole in the Current Sensor such that the arrow on the Current Sensor points towards the AC power source. Then, reattach the hot wire to the AC source.

Step 3: You must supply a cable for connecting the voltage sense pins on the ACM100 to the AC source. For the purposes of these instructions, we will assume that the cable has one black conductor and one white conductor. Install the voltage sense cable as follows:

a.Connect the white wire from one end of the Voltage Sense cable to pin 4 (VANeutral) on the ACM100.

b.Connect the white wire from the other end of the Voltage Sense cable to the neutral wire of the AC source being monitored.

c.Connect the black wire from one end of the Voltage Sense cable to pin 1 (VALine) on the ACM100

d.Connect the black wire from the other end of the Voltage Sense cable to a fuse appropriately sized for the black wire (18 gauge wire minimum and 3 amp fuse or less).

e.Connect the other end of the fuse to the AC source hot wire (the fuse should be placed within 6 inches of the connection to the hot wire).

2.4.2.2 Single-Phase (Phase A, B) Connection

Please refer to Figure 4 for connecting the ACM100 to a single phase, dual line system.

Current

Transformer

Line (Phase B)

Source

 

Fuse

 

 

 

 

Current

 

 

 

 

 

 

 

 

 

Transformer

 

 

 

Line (Phase A)

 

 

 

 

 

 

 

 

 

AC

Fuse

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

9

10 11 12

 

ALine

BLine

CLine

ANeutral

BNeutral

NeutralC

A+

A-

B+

B- C+ C-

 

I I I I I I

 

V V V V V V

 

 

 

 

+

+

U.S.

Europe

120 Volts

220 Volts

60Hz

50Hz

-

-

ACM100 Screw Terminals

Figure 4 – Single-Phase (Dual Line) Connection Diagram

Use the following instructions when you are connecting the ACM100 to a single-phase circuit connected via two hot wires. You will need to install two current transformer and two user- supplied voltage sense cables. The ACM100 comes with a single current transformer so you

Page 6

Revision 1.2

Page 10