![Problem](/images/new-backgrounds/35680/3568079x1.webp)
TROUBLESHOOTING (Continued)
These guidelines should be used by a qualified Maytag Customer Service Center Agent. Call the
Maytag Customer Service Center at
Problem | Cause | Solution | |
|
|
| |
| Blower will not run. |
| |
| A) “ON/OFF” control switch turned off | Turn switch to the “ON” position. | |
| B) Blower unplugged. | Plug blower back into 115 VAC outlet. | |
| C) No power at outlet. | Repair service to outlet. | |
| D) Thermostat defective. | Replace thermostat. | |
| E) Control harness defective. | Replace control harness. | |
NOT ENOUGH | F) High limit control circuit open. | Replace ECO. | |
G) Blower motor defective. | Replace blower assembly. | ||
HOT WATER | |||
Thermostat problems. |
| ||
|
| ||
| A) Thermostat set too low. | Set temperature control higher. | |
| B) Thermostat or ECO defective. | Replace thermostat or ECO as required. | |
| Others. |
| |
| A) Heater undersized. | Reduce hot water use. | |
| B) Low gas pressure. | Contact dealer. | |
| C) Incoming water is unusually cold. | Allow more time for heater to reheat. | |
| D) Leaking hot water pipes or fixtures. | Have plumber check and repair leaks. | |
| A) Not enough dilution air to mix with flue gases. | Proper dilution air must be provided for dilution of flue | |
VENT PIPE TOO HOT |
| temp. Refer to “Installation Instructions” section. | |
B) Dilution air too hot for mixing with flue gases. | Check for heat sources around and/or blockage of | ||
(ABOVE 170OF | |||
| dilution air intake at draft hood. (see page 28). | ||
|
| ||
| C) Wrong burner assembly. | Install correct orifice. | |
| A) Dirt in burner ports. | Turn off heater and gas, clean burner head. | |
YELLOW FLAME | B) Combustion air path restricted. | Check dilution air intake, exhaust venting and air openings | |
| in bottom base pan for obstructions or blockage. | ||
|
| ||
| C) Not enough dilution air. | Check dilution air intake for obstructions or blockage. | |
| A) Water on the floor under heater. | See “Condensation” section. | |
CONDENSATION | B) Water dripping from the blower assembly. | Provide drip “TEE” to catch condensation from horizontal | |
|
| section of exhaust vent close to blower assembly. | |
| Improperly sealed, hot or cold supply connections, | Tighten threaded connections. | |
WATER LEAKS | relief valve, drain valve or thermostat threads. |
| |
Leakage from other appliances or water lines. | Inspect other appliances near the water heater. | ||
| |||
| Condensation of flue products. | See “Condensation” section. | |
| Thermal expansion in closed water system. | Install thermal expansion tank (DO NOT plug T & P valve). | |
LEAKING T & P | Improperly seated valve. | Check relief valve for proper operation (DO NOT plug | |
|
| T & P valve). | |
HOT WATER ODORS | High sulfate or mineral content in water supply. | Drain and flush heater thoroughly then refill. | |
(Refer to Smelly Water) | Bacteria in water supply. | Chlorinate water supply. | |
WATER TOO HOT | Thermostat set too high. | Refer to TEMPERATURE REGULATION. | |
WATER HEATER SOUNDS | Condensation dripping on burner. | See “Condensation” section. | |
Sediment at bottom of heater tank. | Clean sediment from tank. Refer to “Draining” instruction | ||
| |||
| in “Maintenance” section of manual. | ||
|
| ||
SOOTING | Improper combustion. | Refer to “Combustion Air and Ventilation” on pages | |
HEATER LIGHTS BUT GOES | Outlet polarity is reversed. | Test polarity and correct. | |
|
| ||
OUT IN |
|
| |
|
|
|
40