Maytag HRP31275P Venting Throughan Outside Wall, 3” PVC, ABS or CPVC Schedule 40 vent piping

Models: HRN11240P HRP11240P HRN11275P HRP11250P HRP31275P HRN31240P HRN31250P HRN31275P HRP11275P HRP31240P HRP31250P HRN11250P

1 48
Download 48 pages 35.36 Kb
Page 19
Image 19
Venting

Venting

To insure proper venting of this gas-fired water heater, the correct vent pipe diameter must be utilized. Do not install other gas appliances on the same vent with this water heater as this will adversely affect the operation on the water heater.

The combustion and ventilation air flow must not be obstructed.

The power vent water heater requires its own (separate) venting system. It cannot be connected to an existing vent pipe or chimney. It must be terminated to the outdoors. Failure to properly install the venting system can result in asphyxiation, a fire or explosion and cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.

The vent pipe from the water heater must slope upward 1/8” per five feet for any horizontal run.

All vent gases must be completely vented to the outdoors of the structure (dwelling).

FIGURE28.

Chemical vapor corrosion of the flue and vent system may occur. If air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

Horizontal runs must be securely supported at 3 1/2” foot intervals and vertical runs supported at 5 foot intervals.

FIGURE29.

VENTING THROUGHAN OUTSIDE WALL:

75 GALLON 70,000 AND 75,000 BTU/HR MODELS ONLY (See rating plate for BTU/HR rating)

3” PVC, ABS or CPVC Schedule 40 vent piping:

A 3” PVC Schedule 40-45ovent cap with wire screen is supplied with the water heater.

A 3” PVC, ABS or CPVC Schedule 40-90ostreet ell; used to connect the vent pipe to the water heater when the vent pipe is to be turned horizontally directly off the blower (supplied locally).

3” PVC, ABS or CPVC Schedule 40 pipe (must be supplied locally).

FIGURE30.

75 GALLON 70,000 AND 75,000 BTU/HR MODELS ONLY

The water heater requires its own (separate) venting system.

3” PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all 75 gallon 70,000 and 75,000 BTU/HR models.

It cannot be connected to existing vent piping or chimney.

It must terminate horizontally to the outdoors.

19

Page 19
Image 19
Maytag HRP31275P, HRN11250P, HRP31250P manual Venting Throughan Outside Wall, 3” PVC, ABS or CPVC Schedule 40 vent piping