VENTING SYSTEM EXAMPLE INSTALLATIONS

The water heater requires its own (separate) venting system.

2” and 3” PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all 40 and 50 gallon 40,000 BTU/HR models.

It cannot be connected to existing vent piping or chimney.

It must terminate horizontally to the outdoors.

NOTE: See pages 24 and 25 for vertical venting through the roof.

VENTING SYSTEM EXAMPLE INSTALLATIONS

FOR ALL MODELS

The vent piping cannot under any circumstances be run down hill.

FIGURE34.

The vent piping may be installed as follows:

• Horizontal runs require a minimum 1/8” rise per five feet

FIGURE35.

FIGURE36.

FIGURE37.

75 GALLON 70,000 AND 75,000 BTU/HR MODELS

See chart on following page for maximum length.

FIGURE38.

21

Page 21
Image 21
Maytag HRN11275P manual Venting System Example Installations, For All Models, The vent piping may be installed as follows