| 3. Operation |
"Output" tab |
|
| |
|
|
|
|
| Personalisable function | Default setting | Options |
|
|
|
|
| Rated UPS voltage | 230 V | 200 V - 210 V - 220 V - 240 V |
|
|
|
|
| Rated UPS frequency | F = 50 Hz | 60 Hz |
|
|
|
|
| UPS tolerance for | F ± 5 % | F ± 1 % to ± 10 %, in 1 % steps |
| source frequency |
|
|
|
|
|
|
| Overload alarm threshold | 110 % | 0 to 110 %, in 10 % steps |
|
|
|
|
| UPS restart following | Disabled | Enabled (click to add check) |
|
|
|
|
"Bypass" tab |
|
| |
|
|
|
|
| Personalisable function | Default setting | Options |
|
|
|
|
| Transfer to bypass if overload | Enabled | Disabled (click to remove check) |
|
|
|
|
| Transfer to bypass following a fault, whatever the | Disabled | Enabled (click to add check) |
| conditions on the |
|
|
|
|
|
|
bypass
Press button 23 (return to the OFF position).
The connected equipment is no longer supplied with power.