MGETM GalaxyTM 6000 : Specification guide

Parallel UPS, three-phase, 250 to 3000 kVA*

* Power rating for an N+1 redundant configuration

9 - Battery management

As the life of the batteries is very sensitive to operating conditions, the battery shall be managed in an optimum manner.

In addition to the devices indicated in section 8.4 "Batteries", the battery-management system shall include the features listed below.

9.1 - Self-test

The battery shall include a self-test system initiated in two manners:

ωas necessary by a manual command;

ωautomatically at user-defined intervals.

This self-test system shall update the battery parameters and detect any abnormal deterioration to facilitate preventive maintenance.

9.2 - Measurement of actual backup time

The battery function shall be combined with a system that continuously monitors the actual backup time available (AC source present) or remaining (AC source absent), according to the actual load on the UPS, the battery temperature and the age of the battery.

9.3 - Digital battery monitoring

Each UPS shall be equipped with a system for battery digital management.

Based on a number of parameters (percent load, temperature, battery type and age), the system shall control the battery charge voltage and continuously calculate:

ωThe true available backup time

ωThe remaining service life.

9.4 - Block by block monitoring

To further optimise battery availability and service life, it shall be possible to equip each UPS with an optional system to continuously monitor all battery strings and display a block by block failure prediction.

The system shall include the functions listed below.

ωContinuous measurement of the voltage of each block.

ωContinuous measurement of the internal resistance.

ωIdentification of faulty blocks (trend curves).

ωPossibility of replacing individual blocks.

ωRemoting of all information via Ethernet, dry contacts or JBus.

APC By Schneider Electric

Edition - 03/2009

Spec. E - 11

Page 11
Image 11
MGE UPS Systems 6000 manual Battery management, Self-test, Measurement of actual backup time, Digital battery monitoring