MGETM GalaxyTM 6000 : Specification guide

Parallel UPS, three-phase, 250 to 3000 kVA*

* Power rating for an N+1 redundant configuration

12 - Standards and tests

12.1 - Standards

All equipment shall be designed and built in accordance with accepted engineering practice and applicable international standards, in particular the standards listed below.

ωIEC 6014A-4: UPS - Performance.

ωIEC 62040-1 and EN 62040-1: UPS - Safety.

ωIEC 62040-2 and EN 62040-2: UPS - Electromagnetic compatibility - [level C3 / C2 class A is optional].

ωIEC 62040-3 and EN 62040-3: UPS - Performance.

ωIEC 60950 / EN 60950: Safety of IT equipment, including electrical business equipment.

ωIEC 61000-2-2: Compatibility levels for low-frequency conducted disturbances and signalling in public low- voltage power supply systems.

ωIEC 61000-4: EMC - Electrical fast transient/burst immunity.

ωIEC 439: Low-voltage switchgear and controlgear assemblies.

ωIEC 60529: Degrees of protection provided by enclosures (IP Code).

ωISO 3746: Sound power levels.

ωCE marking.

What is more, the equipment must comply with environmental-protection standards, with production taking place on premises certified ISO 14001. The UPS design procedure shall be covered by an ISO 9001 quality system as well as a dependability study to ensure maximum reliability.

12.2 - Certification of conformity

The manufacturer shall provide, on request, a complete qualification file demonstrating compliance with the above standards. What is more, the indicated levels of performance shall be confirmed by certification from independent laboratories (e.g. TÜV or Veritas).

13 - Test procedures and quality system

13.1 - Test procedures

The UPS manufacturer shall provide proof of a stringent Quality Assurance programme.

In particular, the main equipment manufacturing stages shall be sanctioned by appropriate tests such as:

ωincoming components inspection, discrete subassembly testing;

ωcomplete functional checks on the final product.

Equipment shall undergo on-load burn-in before leaving the factory.

Final inspection and adjustments shall be documented in a report drawn up by the supplier’s Quality Inspection department.

ISO 9001 or 9002 certification of the production site is compulsory.

13.2 - Quality system

The UPS design procedure shall be covered by an ISO 9001 quality system as well as a dependability study to ensure maximum reliability.