MGETM GalaxyTM 6000 : Specification guide
Parallel UPS, three-phase, 250 to 3000 kVA*
* Power rating for an N+1 redundant configuration
Inverter |
|
|
|
|
|
|
|
| Volts | yes |
|
| |
|
|
|
| |||
adjustable | ± 3 % |
|
| yes |
|
|
|
|
|
| |||
± 1% |
|
| yes |
|
| |
|
|
|
| |||
Voltage transients | ± 3% (load from 0 to 100 or 100 to 0 %) | yes |
|
| ||
|
| |||||
Output voltage distortion at Pn | THDU | yes |
|
| ||
|
| |||||
| THDU | yes |
|
| ||
|
|
| ||||
Output frequency |
|
| Hz | yes |
|
|
|
|
|
| |||
Variation in output frequency | ± 0.5 Hz | yes |
|
| ||
|
| |||||
adjustable | ± 0.25 Hz to 2 Hz | yes |
| |||
| ||||||
Frequency synchronisation with an external | ± 8 % of rated frequency | yes |
| |||
|
| |||||
source |
|
|
| yes |
|
|
Overload capacity | 125% | In for 10 minutes |
| |||
|
| |||||
| 165% | In for 1 minute | yes |
| ||
|
|
| ||||
Current limiting | 233% | In for 150 milliseconds | yes |
| ||
|
| |||||
Crest factor | up to 3:1 | yes |
| |||
|
|
no no no no no no no no
non no
no no no no
Static bypass
Static bypass |
| yes |
depending on power | yes | |
Maintenance bypass |
| yes |
no no
no
Efficiency
Normal mode | > 95% at Pn, > 92 % at Pn/2 | yes |
no
User interface
Graphic display 15 languages | selection of operating language | yes |
personalisation menu | with password | yes |
display | measurements, status, events, graphs | yes |
event log | yes | |
Controls | ON, OFF, EPO terminal block | yes |
Status indications with mimic panel | Audio alarm, LEDs | yes |
no no no no no no
APC By Schneider Electric | Edition - 03/2009 | Spec. E - 19 |