MGETM GalaxyTM 6000 : Specification guide
Parallel UPS, three-phase, 250 to 3000 kVA*
* Power rating for an N+1 redundant configuration
1 - UPS definition
1.1 - Purpose
The purpose of this specification is to define the design, manufacture and testing characteristics required in view of supplying, putting into operation and maintaining an Uninterruptible Power Supply (referred to as a UPS in the rest of this document).
The UPS shall be designed to supply dependable electric power to:
For information purposes | MTBF in | Non availability |
| hours | |
|
| |
475000 | ||
|
|
|
Active modular redundancy n+1 with centralized |
|
|
bypass |
|
|
2 UPS units | 3.11x106 | |
3 UPS units | 2.42x106 | |
4 UPS units | 1.97 x106 | 5.07 |
5 UPS units | 1.67x106 | 6 |
6 UPS units | 1.44x106 | 6.95 |
1.2 - Brief description
The UPS system shall be made up of …[ 2 / 3 / 4 / 5 / 6 ]…identical
Each UPS unit shall have a unit rating of …[ 250 / 300 / 400 / 450 500 / 600 / 800 ]… kVA, made up of the following components, described in this specification:
ωrectifier;
ωbattery charger;
ωinverter;
ωbattery;
ωa
In addition, the UPS shall be equipped with:
…………………………………………………………………………………………………………………………..
() for parallel connection of two single UPS units, with redundancy)
ωstatic bypass (via a static switch) on each unit;
ωmanual maintenance bypass on each unit;
ωuser and communications interface on each unit.
…………………………………………………………………………………………………………………………..
() for parallel connection with an external
ωstatic bypass (via a static switch) on each unit;
ωcommon, external, maintenance bypass for all units, installed in a cabinet;
ωuser and communications interface on each unit.
…………………………………………………………………………………………………………………………..
() for parallel connection with a
ωa centralized bypass shall be made up of the following components:
-static bypass (via a static switch);
-manual maintenance bypass.
The centralized bypass shall be sized to support the entire load. Consequently, its power rating shall be …[ 250 / 500 / 800 / 1200 / 2000 …] kVA.
ωa user and communications interface for the entire UPS system.
The UPS system shall also comprise any and all other devices required for safe operation and maintenance, including circuit breakers, switches, etc.
The UPS system shall ensure continuity of electric power to the load within the specified tolerances, without interruption upon failure or deterioration of the normal AC source (utility power) for a maximum protection time determined by the capacity of the backup batteries installed.