Miele DA 3190 EXT, DA 3160 EXT Condensate trap, Silencer, Connection for air extraction

Models: DA 3160 EXT DA 3190 EXT

1 40
Download 40 pages 46.84 Kb
Page 32
Image 32
Condensate trap

Connection for air extraction

Important:

If the exhaust ducting is to run through rooms, ceiling space etc. where there may be great variations in temperature between the different areas, the problem of condensation will need to be addressed. The exhaust ducting will need to be suitably insulated.

Condensate trap

(optional accessory)

In addition to insulating the exhaust ducting, we recommend that a suitable condensate trap is installed to collect and evaporate any condensate which may occur. Condensate traps are available for C 125 mm or C 150 mm ducting.

When installing a condensate trap, ensure that it is positioned vertically and if possible directly above the exhaust connection. The arrow on the housing indicates the direction of air-flow.

Silencer

To achieve even further reductions in noise levels, a special silencer can be fitted in the ducting system.

It can be sited at any suitable position in the ducting system between the cooker hood and the external motor on EXT model cooker hoods.

On extraction models, it can be fitted nearest the ducting outlet to the outside to reduce neighbourhood noise.

On recirculation models, it can be fitted in between the fan and the deflector.

32

Page 32
Image 32
Miele DA 3190 EXT, DA 3160 EXT installation instructions Condensate trap, Silencer, Connection for air extraction