4-5. Electrical Service Guide

NOTICE − INCORRECT INPUT POWER can damage this welding power source. Phase to ground voltage shall not exceed +10% of rated input voltage.

NOTICE − Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input voltage is outside this range, output may not be be available.

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda- tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.

 

 

 

Single-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

60.8

54.6

 

29.7

 

25.4

19.9

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

70

60

35

 

30

25

Normal Operating 3

80

80

45

 

40

30

Min Input Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

Max Recommended Input Conductor Length In Feet (Meters)

72

89

 

176

 

140

219

(22)

(27)

 

(54)

 

(43)

(67)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

8

8

 

10

 

12

12

 

 

 

Three-Phase

 

 

 

 

 

 

 

 

 

 

Input Voltage

208

230

 

400

 

460

575

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

40.4

36.1

 

20.6

 

17.8

14.1

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

 

 

 

 

Time-Delay 2

45

40

25

 

20

15

Normal Operating 3

60

50

30

 

25

20

Min Input Conductor Size In AWG/Kcmil 4

8

10

 

12

 

14

14

Max Recommended Input Conductor Length In Feet (Meters)

119

96

 

175

 

150

234

(36)

(29)

 

(53)

 

(46)

(71)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil 4

10

10

 

12

 

14

14

Reference: 2005 National Electrical Code (NEC) (includes article 630)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” (65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

OM-2251 Page 16

Page 20
Image 20
Miller Electric 350 VS manual Electrical Service Guide, Single-Phase Input Voltage, Input Amperes At Rated Output