Miller Electric Big Blue 251D manual Operating Auxiliary Equipment

Models: Big Blue 251D

1 60
Download 60 pages 39.47 Kb
Page 24
Image 24

SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. 120 Volt Duplex And Optional GFCI Receptacles

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

 

 

 

4

3

YIf unit does not have GFCI re- ceptacles, use GFCI-pro- tected extension cord.

1120 V 15 A AC Receptacle RC1

2120 V 15 A AC Receptacle RC2

3120 V 20 A AC GFCI Receptacles GFCI1 And GFCI2 (Optional)

Receptacles supply 60 Hz single- phase power at weld/power speed.

4Circuit Breakers CB1 And CB2

CB1 protects RC1/GFCI1 and CB2 protects RC2/GFCI2 from over- load. If CB1 or CB2 opens, the receptacle does not work.

.If a circuit breaker continues to open, contact Factory Autho- rized Service Agent.

If a ground fault is detected, GFCI Reset button pops out and receptacle does not work. Check for faulty tools plugged in receptacle. Press button to reset.

.At least once a month, run en-

gine at weld/power speed and press test button to verify GFCI is working properly.

Maximum output from each duplex receptacle is 1.8 kVA/kW, and 3 kVA/kW from all receptacles. Gen- erator power is not affected by weld output.

EXAMPLE: If 15 A is drawn from RC1, only 10 A is available at RC2:

(120 V x 15 A) + (120 V x 10 A) = 3.0 kVA/kW

Ref. 206 029

OM-480 Page 20

Page 24
Image 24
Miller Electric Big Blue 251D manual Operating Auxiliary Equipment, Volt Duplex And Optional Gfci Receptacles