7-2. 240 Volt Duplex Receptacle (Optional)

1

2

1

YIf unit does not have GFCI re- ceptacles, use GFCI-pro- tected extension cord.

1240 V 15 A AC Receptacle RC1

Receptacle supplies 60 Hz single- phase power at weld/power speed. Maximum output is 3 kVA/kW.

2Circuit Breakers CB1 And CB2

CB1 and CB2 protect the receptacles from overload. If CB1 or CB2 opens, the 240 V receptacle and half of the 120 V receptacle does not work. 120 volts may still be present at the 240 V receptacle.

.If a circuit breaker continues to

open, contact Factory Autho- rized Service Agent.

Combined output of all receptacles is 3 kVA/kW. Generator power is not affected by weld output.

EXAMPLE: If 10 A is drawn from the 240 V receptacle, only 5 A is avail- able at the 120 V receptacle:

(240 V x 10 A) + (120 V x 5 A) = 3.0 kVA/kW

Ref. 206 029 / 174 408

OM-480 Page 21

Page 25
Image 25
Miller Electric Big Blue 251D Volt Duplex Receptacle Optional, 240 V 15 a AC Receptacle RC1, Circuit Breakers CB1 And CB2