8-3. Optional Generator Power Receptacles

European Receptacle

5

6

Australian Receptacle

5

6

South African Receptacle

5

6

1

2

1

3

1

4

 

 

 

 

 

 

1120 V 20 A AC GFCI Receptacle GFCI1

2240 V 16 A AC European Receptacle RC1

3240 V 15 A AC Australian Receptacle RC1

4240 V 15 A AC South African Receptacle RC1

Receptacles supply 60 Hz single- phase power at weld/power speed.

If a ground fault is detected, the GFCI Reset button pops out and the receptacle does not work. Check for faulty tools plugged in receptacle. Press button to reset GFCI1.

.At least once a month, run en- gine at weld/power speed and press test button to verify GFCI is working properly.

5Circuit Breaker CB2

6Circuit Breaker CB3

CB2 protects GFCI1 from overload. If CB2 opens, GFCI1 does not work. Press button to reset breaker.

CB3 protects RC1 from overload. If CB3 opens, RC1 does not work. Press button to reset breaker.

.If a circuit breaker continues to open, contact Factory Autho- rized Service Agent.

.Generator power is not af- fected by weld output.

Maximum output is 2.4 kVA/kW from GFCI1 and 4 kVA/kW from RC1. Maximum output from all re- ceptacles is 4 kVA/kW.

EXAMPLE: If 13 A is drawn from RC1, only 7 A is available at GFCI1:

(240 V x 13 A) + (120 V x 7 A) = 4.0 kVA/kW

191 624

OM-496 Page 40

Return To Table Of Contents

Page 46
Image 46
Miller Electric Big Blue 452P manual Optional Generator Power Receptacles, 240 V 15 a AC South African Receptacle RC1