3-11. Electrical Service Guide

Input Voltage

230

460

575

 

 

 

 

Input Amperes At Rated Output

69

34.5

27.5

 

 

 

 

Max Recommended Standard Fuse Rating In Amperes 1

 

 

 

Time-Delay 2

80

40

30

Normal Operating 3

100

50

40

 

 

 

 

Min Input Conductor Size In AWG 4

4

8

10

 

 

 

 

Max Recommended Input Conductor Length In Feet (Meters)

237

422

444

(72)

(129)

(135)

 

 

 

 

 

Min Grounding Conductor Size In AWG 4

8

10

10

 

 

 

 

Reference: 1999 National Electrical Code (NEC)

1Consult factory for circuit breaker applications.

2“Time-Delay” fuses are UL class “RK5” .

3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).

4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

3-12. Placing Jumper Links

Y Disconnect and lockout/tag- out input power before installing or moving jumper links.

Check input voltage available at site.

1 Jumper Link Label

Check label − only one is on unit.

2 Jumper Links

Move jumper links to match input voltage.

Close and secure access door, or go on to Section 3-13.

1

230 VOLTS

460 VOLTS

575 VOLTS

 

 

Ref. S-174 973-A

2

Tools Needed:

 

3/8 in

 

3/8 in

Do not overtighten

 

jumper link nuts.

Ref. 800 103-A