1. START-UP

1. Turn on Input breaker and the Battery breaker (10KVA) on the rear panel after checking the power wiring. The cooling fans
should be rotating and the control panel should show the display as below.

Page A1

APPLICATION NOTES
Figure 1.1-1 Bypass Mode
(Load LED display depends of load level)
2. Then press the “|” button. After 10 seconds, the control panel will become what is shown in Fig. 1.2-1.
3. Turn on the output breaker located on the rear panel to provide power to the load.
Figure 1.2-1 Inverter Mode
4. The UPS should be successfully started.
5. If the UPS is in normal operation, the user can run a battery-mode test by pushing the “ON” button. The four LED’s on
the lower half of the control panel (i.e. line, bypass, battery, inverter) will flash.
6. To turn off the UPS, push the “OFF” button, then turn off the Input breaker and the Battery breaker (10KVA).

2. OUTPUT VOLTAGE SETTING

Four voltage options are available (208V, 220V, 230V , 240V). Users can set the desired voltage through DIP SWITCHES located
on the rear panel. The output voltage can be switched according to the instructions below:
1. Press the “OFF “ button to turn off the UPS.
2. Switch the output breaker to the OFF position.
3. Turn off Input breaker and the Battery breaker (10KVA).
4. Wait until the fans stop turning, then switch the DIP SWITCHES to the desired voltage position. Table 2-1, also printed under
DIP SWITCHES, shows these four positions and their corresponding voltage levels.
5. After setting the DIP switches, turn on the Input breaker and the Battery breaker (10KVA), press the “| “ button and then turn
on the output breaker. The voltage setting has been successfully changed when the UPS switches to INVERTER mode.
Table 2-1