2.3 WIRING DESCRIPTION

The wiring method for the MCP SERIES is shown in Figure A.

Figure A - Wiring Diagram for MCP 6001, & MCP10001

REAR VIEW

Wiring Instructions:

1.Utility panel circuit breaker required is 35A or larger

2.Utility wire guage must be 8 guage or larger.

3.Connect utility per drawing.

4.Connect output load connections and jumper wires for correct voltages per drawings.

5.Use proper size AWG wires for all connections.

6KVA

O NLY

10KVA

O N L Y

NOTE: PARA SYSTEMS DOES NOT PROVIDE AC OUTPUT OVERCURRENT PROTEC- TION. OUTPUT OVERCURRENT PROTECTION IS TO BE PROVIDED BY THE USER.