1.3PRODUCT SPECIFICATIONS ELECTRICAL SPECIFICATIONS

Model

Power

Freq.

Input

Output

No.

Rating

(Hz)

 

 

 

 

 

 

Voltage

Current

Voltage

Current

 

 

 

 

MCP 6001

6KVA

50/60

 

170-276

33A

120, 120/120, 208,

50, 25/25, 28.8,

 

4.2KW

 

 

VAC

 

120/208, 240, 120/240V

25/28.8, 25, 25/25A

MCP10001

10KVA

50/60

 

170-276

56A

120, 120/120, 208,

83.3, 41.7/41.7, 48.1,

 

7KW

 

 

VAC

 

120/208, 240, 120/240V

41.7/48.1, 41.7, 41.7/41.7A

INPUT

Voltage:

As listed

Phase:

single phase with ground

Frequency:

50/60Hz +/- 5%, auto selection

Power factor:

>/= 0.97

OUTPUT

Output voltage regulation:

+/-3%

Power factor:

0.7 lag to unity

Frequency regulation:

+/-5%, phase lock to input under normal conditions, +/-0.5% of nominal frequency,

 

under normal operation or battery mode.

Distortion:

+/-3.0% THD at full linear load, +/-7% THD at full non-linear load

Overload Capacity:

>130% +/-10% for 200 ms, 105% for 10 second

Load Crest Ratio

3:1 maximum

OPERATING ENVIRONMENT

Ambient temperature:

10 to 40 degrees Centigrade

Operation humidity:

20% to 90%, non-condensing

Altitude:

less than 1500M above sea level

Storage temperature:

-15 to 40º C

MECHANICAL SPECIFICATIONS

Model Number

Dimensions

Weight

 

H x W x D

Net (Shipping)

MCP 6001

31.5 x 10.25 x 23.25 in.

296(311.6)lb.

 

80 x 26 x 59 cm

134.3(141.3)Kg

 

 

 

MCP10001

38 x 13.5 x 26.5 in.

519.6(552.2)lb.

 

96.5 x 34.3 x 67.3 cm

235.7(250.5)Kg

 

 

 