Mitsubishi Electronics 9700 Series technical manual UPS Cabinet Terminal Relay ContactTerminal

Models: 9700 Series

1 65
Download 65 pages 22.66 Kb
Page 28
Image 28
A) Output Contacts(for external alarm annunciation)

MITSUBISHI

9700 SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

2-10

A) Output Contacts(for external alarm annunciation)

Output contacts consist of form Adry type contacts. Rated value of all output contacts is 120Vac/0.5Aac or 30Vdc/1Adc. Operate all dry contacts at their rated values or lower. Figure 2.16 illustrates typical installation. The external relay can also be a lamp, LED, computer, etc.

FIGURE 2.16 Control Wiring for External Contacts

UPS Cabinet

UPS CabinetExternal to UPS Cabinet Terminal

Relay

ContactTerminal

External to UPS Cabinet

Relay

Coil

Details of output alarm contacts : Power

Source

Details of output alarm contacts :

Terminals 22 to 21 "Load on Bypass" contact (OUT0)

Activated when the power is supplied from the static bypass input. Terminals 24 to 26 "Load on Inverter" contact (OUT1)

Activated when the power is supplied by the inverter. Terminals 25 to 26 "Battery Operation" contact (OUT2)

Activated when the battery is operating following an AC power failure. Terminals 27 to 28 Converter Operationcontact (OUT3)

Activated when the converter is operating. Terminals 29 to 30 "UPS failure" contact

Activated when a major fault has occurred to the system. Terminals 31 to 32 "UPS failure" contact

Activated when a major fault has occurred to the system. Terminals 34 to 33 "Battery Low Voltage" contact (OUT4)

Activated when DC voltage dropped below discharge end during inverter operation.

Terminals 35 to 34 "Overload" contact (OUT5)

Activated when an overload has occurred to the system.

MITSUBISHI ELECTRIC 9700 SERIES UPS

Page 28
Image 28
Mitsubishi Electronics 9700 Series UPS Cabinet Terminal Relay ContactTerminal, Details of output alarm contacts