| MITSUBISHI | 9700 SERIES UPS |
|
|
| Page Number: | |||||
| ELECTRIC | OWNERS / TECHNICAL MANUAL | |||||||||
| |||||||||||
TABLE 1.4 Detail of Specifications |
|
|
|
|
|
|
|
| |||
Rated Output kVA | 100 |
| 150 |
| 225 |
|
| 300 |
| 375 | |
Rated Output kW | 80 |
| 120 |
| 180 |
|
| 270 |
| 338 | |
|
| AC INPUT | CHARACTERISTICS |
|
|
| |||||
Configuration | 3 phase, 3 wire |
|
|
|
|
|
| ||||
Voltage | 208 V, 480 V, 600 V +10% ~ |
|
|
| |||||||
Input Power Factor | 0.98 Typical |
|
|
|
|
|
|
|
| ||
Frequency | 60 Hz ± 5% |
|
|
|
|
|
|
|
| ||
Reflected Current THD | 3% max. at 100% load; 5% max. at 50% load |
| |||||||||
|
| STATIC BYPASS INPUT |
|
|
| ||||||
Configuration | 3 phase, 3 or 4 wire |
|
|
|
|
|
| ||||
Voltage | 120/208 V, 277/480 V, 346/ 600 V | ± 10% |
|
| |||||||
Frequency | 60 Hz (± 3% Tracking window) |
|
|
| |||||||
|
|
| BATTERY |
|
|
|
|
|
| ||
Type | VRLA, Flooded Lead Acid, Nickel Cadmium |
| |||||||||
Ride Through | Application Specific |
|
|
|
|
|
| ||||
Nominal Voltage | 360 VDC |
|
|
|
|
|
|
|
| ||
Minimum Voltage | 290 VDC |
|
|
|
|
|
|
|
| ||
Number of Cells | 176 ~ 185 |
|
|
|
|
|
|
|
| ||
|
|
| AC OUTPUT |
|
|
|
|
|
| ||
Configuration | 3 phase, 3 or 4 wire |
|
|
|
|
|
| ||||
Voltage | 120/208 V, 277/480 V, 346/ 600 V |
|
|
| |||||||
Voltage Stability | ± 1% |
|
|
|
|
|
|
|
|
| |
Frequency | 60 Hz |
|
|
|
|
|
|
|
| ||
Frequency Stability | ± 0.01% in free running mode |
|
|
| |||||||
Power Factor | 0.8 nominal |
|
|
|
|
| 0.9 nominal |
| |||
Power Factor range | 0.8 ~ 1.0 lagging (within output kW | rating) |
| ||||||||
Voltage THD | 2% maximum THD at 100% Linear Load |
| |||||||||
|
| 5% maximum THD at 100% |
| ||||||||
Transient Response | ± 2% maximum at 100% load step |
|
|
| |||||||
|
| ± 1% maximum at loss or return of AC power |
| ||||||||
|
| ± 5% maximum at load transfer to/from static bypass | |||||||||
Transient Recovery | Less than 1 line cycle |
|
|
|
|
|
| ||||
Voltage Unbalance | 1% maximum at 100% unbalanced load |
| |||||||||
Phase Displacement | 1% maximum at 100% unbalanced load |
| |||||||||
Inverter Overload | 125% for 10 minutes; 150% for 1 sec |
| |||||||||
System Overload | 500% for 2 cycle (with bypass available) |
| |||||||||
Bypass Overload | 125% for 10 minutes |
|
|
|
|
|
| ||||
|
|
|
| ||||||||
Withstand Rating | 65kA* | *:with optional fuses |
| ||||||||
|
|
|
|
|
|
|
|
| |||
|
| ENVIRONMENTAL |
|
|
|
|
|
| |||
Cooling | Forced Air |
|
|
|
|
|
|
|
| ||
Operating Temperature | 2° F ~ 104° | F (0° C ~ 40° | C). Recommended 68° | F ~ 86° F | |||||||
|
| (20° C ~ 30° | C) |
|
|
|
|
|
| ||
Relative Humidity | 5% ~ 95% Non Condensing |
|
|
| |||||||
Altitude | 3300 Feet (1000 meters); 5000 feet @ 0.99 derating | ||||||||||
Location | Indoor (free from corrosive gases and dust) |
| |||||||||
Paint Color | Munsell 5Y7/1 (Beige) |
|
|
|
|
|
|
MITSUBISHI ELECTRIC 9700 SERIES UPS