3.0INSTALLATION AND OPERATION
3.1Transportation and Installation
TABLE 3.1 How to transport and install the system
Transportation | Installation |
|
|
Transport unit with forklift. | Using the holes (4 - 24) pre drilled into the |
Use eye bolts (supplied) to carry with | UPS channel base, anchor the unit using |
overhead crane. | appropriate hardware. |
|
|
Note : Do not transport in a horizontal position. Cabinets should be maintained upright within +/- 15° during handling.
3.2Installation Procedure
A)Note the load tolerance of the floor
Refer to Table 3.2 for list of weights of UPS’s.
TABLE 3.2 List of UPS weights
UPS Capacity (kVA) | 100 | 150 | 225 | 300 | 375 |
Weight (lb.) | 3060 | 3810 | 4960 | 5890 | 6620 |
|
|
|
|
|
|
B)Minimum clearance required for ventilation
Right side | 1.0" (25 mm) (not required when sidecars are used) | |
Left side | 1.0" | (25 mm) (not required when sidecars are used) |
Back side | 0.0" | (0.0 mm) |
Top side | 23.6" (600 mm) (for air flow) |
C)Space requirement for routine maintenance
Allow the following space at the time of installation.
Front | 39.4" (1000 mm) |
Sides | 0.0" (0.0 mm) |
Rear | 0.0" (0.0 mm) |