B) Internal Static Bypass Line (FIGURE 1.2)
The Internal Static Bypass line is a Hard wired line through CB3, contactor 52S which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is
FIGURE 1.2 Single Line Diagram- Bypass Operation | |||
CB |
|
| Static Transfer |
AC Bypass |
|
| |
Input |
|
| Switch |
Use supplied | CB3 |
|
|
MCCB |
|
|
|
| CONVERTER | INVERTER | 52S |
AC input |
|
| Output |
|
|
| |
CB1 |
|
| 52C |
|
|
|
|
|
|
|
|
| CB2 |
| Power Flow | |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| Not in Use |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery cabinet
UPS Module
C) Inverter supply at battery operation (FIGURE 1.3)
FIGURE 1.3 Single Line Diagram - Battery Operation | |||
CB |
|
| Static Transfer |
AC Bypass |
|
| |
Input |
|
| Switch |
Use supplied | CB3 |
|
|
MCCB | CONVERTER | INVERTER |
|
| 52S | ||
AC input |
|
| Output |
|
|
| |
CB1 |
|
| 52C |
|
| CB2 | Power Flow |
|
|
| Not in Use |
Battery cabinet |
| UPS Module |
If the input power is interrupted, the battery will immediately supply the DC power required by the Inverter to maintain continuous AC power to the load. A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.
MITSUBISHI ELECTRIC 9700 SERIES UPS