B) Internal Static Bypass Line (FIGURE 1.2)

MITSUBISHI

9700 SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-4

B) Internal Static Bypass Line (FIGURE 1.2)

The Internal Static Bypass line is a Hard wired line through CB3, contactor 52S which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is de-energized during Start-up before the system is fully operational.

FIGURE 1.2 Single Line Diagram- Bypass Operation

CB

 

 

Static Transfer

AC Bypass

 

 

Input

 

 

Switch

Use supplied

CB3

 

 

MCCB

 

 

 

 

CONVERTER

INVERTER

52S

AC input

 

 

Output

 

 

 

CB1

 

 

52C

 

 

 

 

 

 

 

 

 

CB2

 

Power Flow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not in Use

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery cabinet

UPS Module

C) Inverter supply at battery operation (FIGURE 1.3)

FIGURE 1.3 Single Line Diagram - Battery Operation

CB

 

 

Static Transfer

AC Bypass

 

 

Input

 

 

Switch

Use supplied

CB3

 

 

MCCB

CONVERTER

INVERTER

 

 

52S

AC input

 

 

Output

 

 

 

CB1

 

 

52C

 

 

CB2

Power Flow

 

 

 

Not in Use

Battery cabinet

 

UPS Module

If the input power is interrupted, the battery will immediately supply the DC power required by the Inverter to maintain continuous AC power to the load. A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.

MITSUBISHI ELECTRIC 9700 SERIES UPS

Page 11
Image 11