WARNING 2
This UPS does not include a Bypass Input circuit breaker (MCCB). The Bypass Input contactor (CB3) does not protect against load induced short circuits. The bypass input circuit breaker (MCCB) is field supplied and installed. Breaker(MCCB)'s Specifications are as follows:
Capacity (kVA) | Bypass Voltage (VAC) | Maximum Bypass | Recommended |
|
| Rating (AAC) | Breaker (A) |
|
|
|
|
100 | 208 | 278 | 350 |
|
|
|
|
100 | 480 | 120 | 150 |
|
|
|
|
100 | 600 | 96 | 100 |
|
|
|
|
150 | 208 | 416 | 500 |
|
|
|
|
150 | 480 | 180 | 225 |
|
|
|
|
150 | 600 | 144 | 150 |
|
|
|
|
225 | 208 | 625 | 700 |
|
|
|
|
225 | 480 | 271 | 300 |
|
|
|
|
225 | 600 | 217 | 225 |
|
|
|
|
300 | 480 | 361 | 400 |
|
|
|
|
300 | 600 | 289 | 300 |
|
|
|
|
375 | 480 | 451 | 500 |
|
|
|
|
375 | 600 | 361 | 400 |
|
|
|
|