MITSUBISHI | 9700 SERIES UPS | Page Number: |
ELECTRIC | OWNERS / TECHNICAL MANUAL |
G)Referring to Figures
H)Connect external signal terminal block as needed. Refer to section 2.4 and Figure 2.15 for functional description. 12 AWG, or less, shielded conductor is recommended.
NOTES: 1. Confirm that all UPS internal contactors(breakers) "CB1", "CB2", and "CB3" are open before energizing UPS.
2.UPS power terminals are supplied with bus bar and hardware (12mm diameter Nut/Bolt assembly). It is recommended that compression lugs be used to fasten all input/output power cables. Refer to Table 3.5 for recommended compression lugs and appropriate crimping tool.
3.If three wire source for input and bypass input is utilized, the neutral conductor is the UPS must be banded to ground.
MITSUBISHI ELECTRIC 9700 SERIES UPS