Mitsubishi Electronics MUZ-ANA, MS-AWA, MUY-ANA, MU-AWA, MSY-ANA Expansion Valve Control Lev Control

Models: MUY-ANA MSY-ANA MS-AWA MUZ-ANA MXZ-ANA MSZ-ANA MU-AWA

1 28
Download 28 pages 7.08 Kb
Page 22
Image 22
3-2. EXPANSION VALVE CONTROL (LEV CONTROL)

3-2. EXPANSION VALVE CONTROL (LEV CONTROL)

Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.

Indoor unit status

LEV opening

Stop of all indoor unit

Opening before stop 500 pulse in 15 minutes

When outdoor unit is operating,

COOL : 5 pulse (full closed)

some indoor units stop and

HEAT :140 pulse (slightly opened)

some operate.

 

 

 

Thermostat OFF in

When the outdoor unit operates (When the other indoor unit operates): 5 pulse.

When outdoor unit stops. (When the other indoor unit stops or thermo off):

COOL or DRY mode

Maintain LEV opening before stop 500 pulse in 15 minutes

 

 

 

 

• LEV opening for each indoor unit is determined by adding adjustment in accordance

 

with the number of operating unit and the capacity class to standard opening, based

 

on the operation frequency:

 

Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205

Thermostat ON in

pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)

• After starting operation, adjustment in accordance with intake super heat, discharge

COOL or DRY mode

temperature is included in standard opening. w1

 

 

Note: LEV opening in each frequency at DRY operation and COOL operation is the

 

same. However, velocity and compressor operation frequency controls are

 

different. See 2-3. OPERATIONAL FREQUENCY RANGE

 

(As far as the indoor unit velocity control goes, refer to DRY operation in

 

MICROPROCESSOR CONTROL in indoor unit.)

 

 

 

• When the outdoor unit operates. (When the other indoor unit operates): 140pulse .

Thermostat OFF in HEAT mode

• When the outdoor unit stops. (When the other indoor unit stops or thermo off):

Maintain LEV opening before stop 500 pulse in 15 minutes.

 

 

 

 

• LEV opening for each indoor unit is determined by adding adjustment in accordance

 

with the number of operating unit and the capacity class to standard opening, based

 

on the operation frequency:

Thermostat ON in HEAT mode

Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165

 

pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 3 units operation)

 

• After starting operation, opening becomes the one that adjustment in accordance

 

with discharge temperature was added to basic opening. w1

 

 

w1 LEV opening when the outdoor unit is operating: Upper limit 500 pulse, Lower limit 53pulse.

Determination of LEV standard opening in each indoor unit

• The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below.

(LEV opening is controlled in proportion to the operation frequency.)

Note: Opening is adjusted at the standard opening according to the indoor unit conditions.

However, inclination of standard opening in each point of opening does not change with the original curve.

Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.

Add opening provided in Difference in Operation number in the table below to determined LEV opening for each indoor unit, when 2 or 3 indoor units are operated at the same time.

Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual driving output opening is in a range from 59 to 500 pulse.

22

Page 22
Image 22
Mitsubishi Electronics MUZ-ANA, MS-AWA, MUY-ANA, MU-AWA, MSY-ANA, MSZ-ANA, MXZ-ANA manual Expansion Valve Control Lev Control