Mitsubishi Electronics MSY-ANA, MS-AWA, MUZ-ANA, MUY-ANA, MU-AWA, MSZ-ANA, MXZ-ANA SWING operation

Models: MUY-ANA MSY-ANA MS-AWA MUZ-ANA MXZ-ANA MSZ-ANA MU-AWA

1 28
Download 28 pages 7.08 Kb
Page 11
Image 11
Manual background

<SWING operation>

In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided.

For initial 10 minutes the swing operation is performed in table G~H for quick cooling.

Also, after 10 minutes when the difference of set temperature and room temperature is more than 3.6 degrees, the swing operation is performed in table D~H for more cooling.

The air conditioner repeats the swing operation in various cycle as follows.

A

B

C

D

E

F

G

H

Temperature of indoor

Downward blow time

Horizontal blow time

coil thermistor RT12

(second)

(second)

59°F or less

2

23

59°F to 63°F

5

20

63°F to 64°F

8

17

64°F to 68°F

11

14

68°F to 70°F

14

11

70°F to 72°F

17

8

72°F to 75°F

20

5

more than 75°F

23

2

 

 

 

11

Page 11
Image 11
Mitsubishi Electronics MSY-ANA, MS-AWA, MUZ-ANA, MUY-ANA, MU-AWA, MSZ-ANA, MXZ-ANA manual SWING operation