2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT
1.Outline
The operational frequency is as following:
First, the target operational frequency is set based on the difference between the room temperature and the set tem- perature.
Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.
2.Maximum/minimum frequency in each operation mode.
| COOL | HEAT(MUZ) | DRY | ||||
Applied |
|
|
|
|
|
| |
Minimum | Maximum | Minimum | Maximum | Minimum | Maximum | ||
model | |||||||
| frequency | frequency | frequency | frequency | frequency | frequency | |
|
|
|
|
|
|
| |
| 32 | 70 | 32 | 76 | 32 | 57 | |
|
|
|
|
|
|
| |
| 32 | 73 | 32 | 71 | 32 | 57 | |
|
|
|
|
|
|
| |
| 10 | 82 | 15 | 93 | 10 | 68 | |
| |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| 10 | 87 | 15 | 93 | 10 | 68 | |
| |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| 15 | 110 | 15 | 108 | 15 | 102 | |
| |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
wThe operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.
It is rated frequency or less.
Upper limit
frequency
Maximum |
frequency |
1 hour |
Rated frequency or less
Time
16