2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT

2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT

1.Outline

The operational frequency is as following:

First, the target operational frequency is set based on the difference between the room temperature and the set tem- perature.

Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection, electric current protection and overload protection and also by the maximum/minimum frequency.

2.Maximum/minimum frequency in each operation mode.

 

COOL

HEAT(MUZ)

DRY

Applied

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

Minimum

Maximum

model

 

frequency

frequency

frequency

frequency

frequency

frequency

 

 

 

 

 

 

 

MUZ-A09

32

70

32

76

32

57

 

 

 

 

 

 

 

MUZ-A12

32

73

32

71

32

57

 

 

 

 

 

 

 

MUZ-A15

10

82

15

93

10

68

MUY-A15

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-A17

10

87

15

93

10

68

MUY-A17

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-A24

15

110

15

108

15

102

MUY-A24

 

 

 

 

 

 

 

 

 

 

 

 

 

wThe operation frequency in COOL mode is restricted the upper limit frequency after 1 hour as shown below for dew prevention.

It is rated frequency or less.

Upper limit

frequency

Maximum

frequency

1 hour

Rated frequency or less

Time

16